{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC3F115F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC3F115F7","canonicalUrl":"https://aoctrl.com/schneider/LC3F115F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC3F115F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC3F115F7, star delta starter, 115 A AC-3, 110 V AC 50/60 Hz coil, 3 x 3 NO power poles, plate mount.","salesMarkdown":"It is rated for AC-3 duty (squirrel-cage motor switching) at 115 A operational current up to 440 V AC, and handles motor power from 52 kW at 220/230 V up to 102 kW at 415/440 V, all at 50/60 Hz. The control circuit runs on 110 V AC 50/60 Hz, with a pick-up range of 0.85 to 1.1 Uc and drop-out between 0.35 and 0.55 Uc at 55 °C. Inrush power is 550 VA at 50 Hz, holding at 45 VA — the coil draw drops significantly once sealed, so the control transformer can be sized for the inrush peak. Mounts to a plate (not DIN rail) — plan for bolted connection via M6 terminals on the power circuit, accepting ring lugs up to 95 mm² or busbar cross-section 20 x 3 mm. The control circuit uses screw clamp terminals accepting 1 to 4 mm² flexible or solid wire.","metaTitle":"TeSys F LC3F115F7 Star Delta Starter, 115 A AC-3, 110 V AC","metaDescription":"Schneider Electric TeSys F LC3F115F7 star delta starter. 115 A rated operational current (AC-3), 110 V AC 50/60 Hz control. Motor power up to 102 kW at 415 V. Current production. S","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Range":"TeSys","Category":"18401-WORLD SERVICE PARTS(CTR ACCESS)","Standards":"EN 60947-1 IEC 60947-4-1 IEC 60947-1 EN 60947-4-1 JIS C8201-4-1","Product name":"TeSys F","Starting time":"20 s","Motor power kW":"52 kW 220/230 V AC 50/60 Hz 85 kW 380/400 V AC 50/60 Hz 102 kW 415 V AC 50/60 Hz 102 kW 440 V AC 50/60 Hz","Operating time":"23...35 ms closing 5...15 ms opening","lifecycle_stage":"current","Heat dissipation":"12...16 W","Mounting Support":"Plate","Device short name":"LC3F","Interlocking type":"Without start delta mechanical interlock","Poles description":"3 x 3P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 88.5 lbf.in (10 N.m)","Inrush power in VA":"550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 660 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Operating altitude":"9842.52 ft (3000 m) without derating","Device presentation":"Pre-wired","Control circuit type":"AC 50/60 Hz","Protective treatment":"TH","Utilisation category":"AC-3","Contactor application":"Motor control","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A gG 125 A aM <= 440 V","Maximum operating rate":"2400 cyc/h 131 °F (55 °C)","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 20 x 3 mm Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Power circuit: bolted connection Power circuit: lugs-ring terminals 1 0.1 in² (95 mm²) Power circuit: connector 1 0.1 in² (95 mm²)","IP degree of protection":"IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106","Rated breaking capacity":"920 A conforming to IEC 60947-4-1","Connections Bolt Diameter":"M6","Product or Component Type":"Star delta starter","Irms rated making capacity":"1150 A IEC 60947-4-1","[Uc] control circuit voltage":"110 V AC 50/60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 1500 V VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc at 50/60 Hz (at Drop-out: 0.35...0.55 Uc at 50/60 Hz (at <131 °F (55 °C))","Power Pole Contact Composition":"3 x 3 NO","[Ie] rated operational current":"115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 for power circuit","[Ue] rated operational voltage":"Power circuit <= 1000 V AC 16 Hz 2/3...200 Hz","Hold-in power consumption in VA":"45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) 55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for operation":"23...131 °F (-5...55 °C) -40...158 °F (-40...70 °C) at Uc","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1100 A 104 °F (40 °C) - 10 s 640 A 104 °F (40 °C) - 30 s 520 A 104 °F (40 °C) - 1 min 400 A 104 °F (40 °C) - 3 min 320 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"200 A 104 °F (40 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2406b4a7d768828d996be742c3613b27.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC3F115F7/tesys-f-star-delta-starter-3-x-3p-3-no-115-a-110-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC3F115F7/alternatives.json"},"ai":{"faq":[{"question":"What standards does the LC3F115F7 comply with?","answer":"It complies with EN 60947-1, IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1."},{"question":"What is the rated breaking capacity?","answer":"Rated breaking capacity is 920 A conforming to IEC 60947-4-1."},{"question":"What is the mechanical durability?","answer":"Mechanical durability is 10 million cycles."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC3F115F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC3F115F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}