{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC3F265V7A64","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC3F265V7A64","canonicalUrl":"https://aoctrl.com/schneider/LC3F265V7A64","factsUrl":"https://aoctrl.com/api/mcp/products/LC3F265V7A64","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC3F265V7A64 pre-wired star delta starter, 3 x 3P, 265 A AC-3, 400 V AC 50/60 Hz control, plate mount.","salesMarkdown":"It's rated at 265 A operational current at ≤440 V AC for the power circuit, which translates to 220 kW at 380/400 V AC 50/60 Hz or 250 kW at 440 V AC 50/60 Hz. That's a serious motor starter for a 250 kW pump or compressor on a 440 V line. The control circuit runs on 400 V AC 50/60 Hz, with a pickup range of 0.85 to 1.1 Uc and dropout between 0.35 and 0.55 Uc. Inrush power is 650 VA at 40–400 Hz, cos φ 0.9 at 20 °C. That 400 V coil voltage is common in European industrial panels — it saves a control transformer if your panel already runs 400 V line-to-line. AC-3 means making and breaking a motor at full load, which is harder on contacts than resistive switching. The associated fuse recommendation is 400 A gG or 315 A aM at ≤440 V, so plan your upstream protection accordingly. Rated breaking capacity is 2120 A and making capacity is 2650 A, both per IEC 60947-4-1 — that's the fault-clearing ability if a motor stalls or shorts. The auxiliary contact complement is already built in: 1 NC + 1 NO on the KM1 star contactor, 2 NC + 1 NO on the KM2 line contactor, and 1 NC + 2 NO on the KM3 delta contactor. That covers the standard star-delta interlocking and status feedback without adding auxiliary blocks. Mechanical interlocking between contactors is included — no external linkage needed. This is a plate-mount unit — not DIN-rail. Dimensions are 625 mm wide × 110 mm high × 266 mm deep, so it needs a backplate or sub-panel, not a 35 mm rail. Power connections are bolted, with bar cross-section 32 × 4 mm or ring terminals up to 240 mm². Control wiring uses screw clamp terminals accepting 1 to 4 mm² flexible or solid. Tightening torque is 35 N·m on the power circuit and 1.2 N·m on control — a torque wrench is expected on the power lugs. IP20 front face with shrouds per IEC 60529 and VDE 0106 — that's touch-safe from the front but not sealed against dust ingress. Not for washdown environments.","metaTitle":"Schneider TeSys F LC3F265V7A64 Star Delta Starter, 265 A AC-","metaDescription":"Schneider Electric TeSys F LC3F265V7A64 pre-wired star delta starter. 265 A rated operational current AC-3, 220 kW at 400 V. Active production. IEC/EN 60947-4-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"266 mm","Range":"TeSys","Width":"625 mm","Height":"110 mm","Standards":"EN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1","Product name":"TeSys F","Starting time":"30 s","Motor power kW":"110 kW at 220/230 V AC 50/60 Hz 220 kW at 380/400 V AC 50/60 Hz 220 kW at 415 V AC 50/60 Hz 250 kW at 440 V AC 50/60 Hz","Operating time":"40...65 ms closing 100...170 ms opening","lifecycle_stage":"current","Heat dissipation":"8 W","Mounting support":"Plate","Device short name":"LC3F","Interlocking type":"Mechanical","Poles description":"3 x 3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Inrush power in VA":"650 VA 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Device presentation":"Pre-wired","Control circuit type":"AC at 50/60 Hz","Protective treatment":"TH","Utilisation category":"AC-3","Contactor application":"Motor control","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 6 Gn for 11 ms","Associated fuse rating":"400 A gG at 315 A aM at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid without cable end Power circuit: bar 2 - busbar cross section: 32 x 4 mm Power circuit: bolted connection Power circuit: lugs-ring terminals 1 240 mm² Power circuit: connector 1 240 mm²","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"2120 A conforming to IEC 60947-4-1","Connections Bolt Diameter":"M10","Product or component type":"Star delta starter","Irms rated making capacity":"2650 A conforming to IEC 60947-4-1","[Uc] control circuit voltage":"400 V AC 50/60 Hz","Auxiliary contact composition":"1 NC for KM1 star contactor 1 NO for KM1 star contactor 2 NC for KM2 line contactor 1 NO for KM2 line contactor 1 NC for KM3 delta contactor 2 NO for KM3 delta contactor","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc at 40...400 Hz (at Drop-out: 0.35...0.55 Uc at 40...400 Hz (at <55 °C)","Power Pole Contact Composition":"3 x 3 NO","[Ie] rated operational current":"265 A (at <55 °C) at <= 440 V AC AC-3 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz","Hold-in power consumption in VA":"10 VA 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C -40...70 °C at Uc","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2200 A 40 °C - 10 s 1230 A 40 °C - 30 s 950 A 40 °C - 1 min 620 A 40 °C - 3 min 480 A 40 °C - 10 min","[Ith] conventional free air thermal current":"350 A 40 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b082542a40ffa345f49b1eb19e79fbc.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC3F265V7A64/tesys-f-star-delta-starter-3-x-3p-3-no-265-a-400-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC3F265V7A64/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The headline rating is 265 A at ≤440 V AC in AC-3 duty, which handles motors up to 220 kW at 400 V or 250 kW at 440 V. Control voltage is 400 V AC 50/60 Hz. Mechanical durability is 10 million cycles."},{"question":"What standards does this star delta starter comply with?","answer":"It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C."},{"question":"What mounting does this require?","answer":"Plate mount only — not DIN-rail compatible. Dimensions are 625 mm wide × 110 mm high × 266 mm deep. Power connections are bolted with M10 hardware."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC3F265V7A64","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC3F265V7A64 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}