{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC7K1201M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC7K1201M7","canonicalUrl":"https://aoctrl.com/schneider/LC7K1201M7","factsUrl":"https://aoctrl.com/api/mcp/products/LC7K1201M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K LC7K1201M7, 3-pole contactor, AC-3/AC-3e 12 A at 440 V, 220-230 V AC coil, 1 NC auxiliary contact, screw clamp terminals.","salesMarkdown":"The LC7K1201M7 is a 3-pole contactor from the TeSys K range, rated for AC-3 and AC-3e duty at 12 A up to 440 V. The 12 A rating at 440 V is the current it can make and break in that category, so for a motor drawing, say, 9 A full-load current, this contactor has headroom. The coil is 220-230 V AC, and the control circuit operates reliably between 0.85 and 1.1 times Uc, with dropout below 0.1 Uc at temperatures under 50 °C. Electrical durability is stated per utilisation category: 1.3 million cycles at 12 A in AC-3 and AC-3e, 0.3 million cycles at 20 A in AC-1 (resistive), and 20,000 cycles at 72 A in AC-4 (plugging/inching). These figures give a clear picture of the contactor's expected life in different applications — the AC-4 figure is notably lower, as expected for the severe switching duty of reversing or inching. The B10d value of 1,369,863 cycles at nominal load (per EN/ISO 13849-1) supports use in safety-related control circuits. The contactor mounts on a plate or DIN rail, with a footprint of 45 mm wide, 58 mm high, and 57 mm deep. Screw clamp terminals accept 1.5 to 4 mm² solid or flexible cable (one or two conductors), with a tightening torque of 0.8 to 1.3 N·m. The 3 W heat dissipation should be factored into the enclosure's thermal budget, especially in a densely populated cabinet.","metaTitle":"TeSys K LC7K1201M7 Contactor, 3P, AC-3 12A, 220-230V AC Coil","metaDescription":"Schneider Electric TeSys K LC7K1201M7 contactor, 3 poles, AC-3/AC-3e 12A at 440V, 220-230V AC coil, 1NC auxiliary contact. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","title":"LC7K1201M7","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1","description":"Contactor, TeSys K, 3P, AC-3/AC-3e,440V 12A, aux. 1NC, 220...230V AC coil","Operating time":"30...40 ms coil energisation and NO closing 30 ms coil de-energisation and NO opening","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"3 W","Mounting support":"Plate Rail","Device short name":"LC7K","Poles description":"3P","Tightening torque":"0.8...1.3 N.m - on screw clamp terminals Philips No 2 0.8...1.3 N.m - on screw clamp terminals flat Ø 6 mm 0.8...1.3 N.m - on screw clamp terminals pozidriv No 2","Device application":"Control","Inrush power in VA":"3 VA (at 20 °C)","Operating altitude":"2000 m without derating","Non overlap distance":"0.5 mm","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-3e AC-1 AC-4","Contactor application":"Resistive load Motor control","Electrical durability":"1.3 Mcycles 12 A AC-3 at Ue 1.3 Mcycles 12 A AC-3e at Ue 0.3 Mcycles 20 A AC-1 at Ue 0.02 Mcycles 72 A AC-4 at Ue <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NC","Connections - terminals":"Screw clamp terminals 1 cable(s) 1.5...4 mm²solid Screw clamp terminals 1 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34...2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1.5...4 mm²solid Screw clamp terminals 2 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.34...1.5 mm²flexible with cable end","IP degree of protection":"IP2X conforming to VDE 0106","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Signalling circuit frequency":"<= 400 Hz","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Hold-in power consumption in VA":"3 VA (at 20 °C)","Ambient air temperature for storage":"-50...80 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/da6a10bd6c1780a0cc449ce84ce5058b.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC7K1201M7/contactor-tesys-k-3p-ac3-ac3e440v-12a-aux-1nc-220-230v-ac-coil/"},"ai":{"faq":[{"question":"What standards does the LC7K1201M7 comply with?","answer":"It complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. The flame-retardance rating is V1 per UL 94."},{"question":"What is the coil voltage and power consumption?","answer":"The coil is rated 220-230 V AC. Inrush and hold-in power consumption are both 3 VA at 20 °C. The coil has no built-in suppressor module."},{"question":"What auxiliary contacts does it have?","answer":"It has one normally closed (1 NC) instantaneous auxiliary contact."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC7K1201M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC7K1201M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}