{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LE4D18FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LE4D18FE7","canonicalUrl":"https://aoctrl.com/schneider/LE4D18FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LE4D18FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LE, enclosed DOL starter, 18 A, 115 V AC 50/60 Hz coil, IP65, polycarbonate enclosure.","salesMarkdown":"The LE4D18FE7 is a Schneider Electric TeSys LE enclosed direct-on-line starter — a self-contained motor-starting package rated for AC-3 duty (switching squirrel-cage motors). It integrates a contactor and fuse disconnector in one IP65 polycarbonate enclosure; the thermal overload relay is ordered separately. ## Motor power coverage by supply voltage The starter covers a useful voltage range: 4 kW at 220/230 V, 7.5 kW at 380/400 V, 9 kW at 415 V and 440 V, and 10 kW at 500 V — all at 50/60 Hz. That means one order code handles the common 400 V class motor up to 9 kW and stretches to 10 kW on 500 V supplies. ## Enclosure and environmental fit The polycarbonate body (330 x 186 x 175.5 mm) accepts multiple cable-entry sizes (ISO 20 through ISO 40) on top and bottom, so gland-plate planning is straightforward. Designed to IEC 60947-4-1 (the standard for contactors and motor-starters). The associated fuse rating is 20 A aM (10 x 38 mm), which provides short-circuit protection coordinated with the starter's breaking capacity.","metaTitle":"TeSys LE LE4D18FE7 Enclosed DOL Starter, 18 A, 115 V AC Coil","metaDescription":"Active-production TeSys LE enclosed DOL starter, 18 A thermal current, 115 V AC coil, IP65, AC-3 motor switching up to 10 kW at 500 V. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Depth":"175.5 mm","Range":"TeSys","Width":"186 mm","title":"LE4D18FE7","Height":"330 mm","Material":"Polycarbonate","Standards":"IEC 60947-4-1","description":"TeSys LE - enclosed DOL starter - 18 A - 115 V AC coil","Control type":"Push-button start green I Push-button stop/reset red O","Product name":"TeSys LE","Motor power kW":"10 kW at 500 V AC 50/60 Hz 4 kW at 220/230 V AC 50/60 Hz 9 kW at 415 V AC 50/60 Hz 9 kW at 440 V AC 50/60 Hz 7.5 kW at 380/400 V AC 50/60 Hz","lifecycle_stage":"current","Device short name":"LE4D","Cable entry number":"2 ISO20 top 2 ISO25 top 2 ISO32 top 2 ISO40 top 2 ISO20 bottom 2 ISO25 bottom 2 ISO32 bottom 2 ISO40 bottom","Device application":"Standard","Device composition":"Thermal overload relay ordered separately Contactor Fuse disconnector","Utilisation category":"AC-3","Associated fuse rating":"20 A 10 x 38 mm aM","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP65 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"115 V AC 50/60 Hz","Ambient air temperature for operation":"-5...40 °C","[Ith] Conventional free air thermal current":"18 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/266225d017ac72b2027e0c00bebdf15e.pdf","sourceUrl":"https://www.se.com/vn/en/product/LE4D18FE7/tesys-le-enclosed-dol-starter-18-a-115-v-ac-coil/"},"ai":{"faq":[{"question":"What are the key motor power ratings for this starter?","answer":"It handles 4 kW at 220/230 V, 7.5 kW at 380/400 V, 9 kW at 415 V and 440 V, and 10 kW at 500 V, all AC-3 duty at 50/60 Hz."},{"question":"What enclosure protection does the LE4D18FE7 offer?","answer":"IP65 (dust-tight and protected against water jets) and IK07 (impact resistance), in a polycarbonate housing."},{"question":"Does the LE4D18FE7 include a thermal overload relay?","answer":"No — the thermal overload relay is ordered separately. The unit ships as a contactor and fuse disconnector in the enclosure."},{"question":"What standard does this starter comply with?","answer":"IEC 60947-4-1, the international standard for contactors and motor-starters."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LE4D18FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LE4D18FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}