{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG1K065M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG1K065M7","canonicalUrl":"https://aoctrl.com/schneider/LG1K065M7","factsUrl":"https://aoctrl.com/api/mcp/products/LG1K065M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LG enclosed DOL starter, LG1K065M7, 6 A AC-3, 220/230 V AC 50/60 Hz coil, IP55, IK07.","salesMarkdown":"The Schneider LG1K065M7 is an enclosed direct-on-line (DOL) starter from the TeSys LG range, combining a switch disconnector, a contactor, and provision for a circuit breaker (ordered separately) in a single polycarbonate enclosure. It is rated for 6 A in AC-3 duty (motor switching) with a 220/230 V AC 50/60 Hz control coil. The IP55 and IK07 ratings mean it withstands water jets and 2 J impact — suitable for washdown or light industrial environments where the starter needs to be mounted near the motor, not locked in a clean panel. The enclosure measures 175 mm wide by 165 mm high by 165 mm deep, with cable entries: 4 × Pg 13 + 2 × Pg 16 at top and bottom. The control interface includes a white push-button start, a black push-button stop, and a red rotary emergency stop handle. This part is obsolete per the manufacturer. The AC-3 rating of 6 A at 400 V (implied by the standard IEC 60947-4-1) means it switches a motor load up to roughly 3 kW at 400 V three-phase. If your motor is larger, or if you need a different coil voltage, the obsolete status means you will be looking at a replacement from the current TeSys range — verify the mounting footprint and gland positions against the original panel cutout. The LG1K065M7 complies with IEC 60204-1 (safety of machinery — electrical equipment) and IEC 60947-4-1 (contactors and motor-starters). The IP55 enclosure and IK07 impact resistance are certified to IEC 60529.","metaTitle":"Schneider LG1K065M7 TeSys LG Enclosed DOL Starter, 6 A AC-3","metaDescription":"Schneider LG1K065M7 is an obsolete TeSys LG enclosed DOL starter, 6 A AC-3, 220/230 V AC coil. Sourced to order against an RFQ. IP55, IK07.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"165 mm","Width":"175 mm","Height":"165 mm","Current":"6 A AC-3","Material":"Polycarbonate","IP Rating":"IP55","Application":"Safety","Coil Voltage":"220/230 V AC 50/60 Hz","Product Status":"Active","Utilization Category":"AC-3","Main Product Or Component Type":"Enclosed DOL starter"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/359eed0090bdecb94af354f974b8c2e4.pdf","sourceUrl":"https://www.se.com/be/en/product/LG1K065M7/tesys-lg-enclosed-dol-starter-6-a-220-230-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG1K065M7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG1K065M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG1K065M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}