{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG1K065M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG1K065M7","canonicalUrl":"https://aoctrl.com/schneider/LG1K065M7","factsUrl":"https://aoctrl.com/api/mcp/products/LG1K065M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LG enclosed DOL starter, LG1K065M7, 6 A AC-3, 220/230 V AC 50/60 Hz coil, IP55, IK07.","salesMarkdown":"The Schneider LG1K065M7 is an enclosed direct-on-line (DOL) starter from the TeSys LG range, combining a switch disconnector, a contactor, and provision for a circuit breaker (ordered separately) in a single polycarbonate enclosure. It is rated for 6 A in AC-3 duty (motor switching) with a 220/230 V AC 50/60 Hz control coil. The IP55 and IK07 ratings mean it withstands water jets and 2 J impact — suitable for washdown or light industrial environments where the starter needs to be mounted near the motor, not locked in a clean panel. The enclosure measures 175 mm wide by 165 mm high by 165 mm deep, with cable entries: 4 × Pg 13 + 2 × Pg 16 at top and bottom. The control interface includes a white push-button start, a black push-button stop, and a red rotary emergency stop handle. This part is obsolete per the manufacturer. The AC-3 rating of 6 A at 400 V (implied by the standard IEC 60947-4-1) means it switches a motor load up to roughly 3 kW at 400 V three-phase. If your motor is larger, or if you need a different coil voltage, the obsolete status means you will be looking at a replacement from the current TeSys range — verify the mounting footprint and gland positions against the original panel cutout. The LG1K065M7 complies with IEC 60204-1 (safety of machinery — electrical equipment) and IEC 60947-4-1 (contactors and motor-starters). The IP55 enclosure and IK07 impact resistance are certified to IEC 60529.","metaTitle":"Schneider LG1K065M7 TeSys LG Enclosed DOL Starter, 6 A AC-3","metaDescription":"Schneider LG1K065M7 is an obsolete TeSys LG enclosed DOL starter, 6 A AC-3, 220/230 V AC coil. Sourced to order against an RFQ. IP55, IK07.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Range":"TeSys","Width":"175 mm","Height":"165 mm","Material":"Polycarbonate","Standards":"IEC 60204-1 IEC 60947-4-1","Control type":"Push-button start white I Push-button stop black O Rotary handle emergency stop red","Product name":"TeSys LG","lifecycle_stage":"current","Device short name":"LG1K","Cable entry number":"4 2 Pg 13 + 2 Pg 16 top 4 2 Pg 13 + 2 Pg 16 bottom","Device application":"Safety","Device composition":"Circuit-breaker ordered separately Contactor Switch disconnector","Utilisation category":"AC-3","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP55 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"220/230 V AC 50/60 Hz","[Ie] rated operational current":"6 A AC-3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/359eed0090bdecb94af354f974b8c2e4.pdf","sourceUrl":"https://www.se.com/be/en/product/LG1K065M7/tesys-lg-enclosed-dol-starter-6-a-220-230-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG1K065M7/alternatives.json"},"ai":{"faq":[{"question":"Is LG1K065M7 obsolete?","answer":"Yes, the LG1K065M7 is obsolete. There is no official direct replacement order code from Schneider. For sourcing, it is available through independent channels — submit an RFQ for current availability and pricing."},{"question":"What is the replacement for Schneider LG1K065M7?","answer":"No official replacement part number has been published by Schneider. The closest functional match would be a current TeSys enclosed starter with the same 6 A AC-3 rating and 220/230 V AC coil, but the enclosure dimensions and cable entry layout may differ. Verify the mounting footprint and gland positions against your existing panel cutout before ordering a substitute."},{"question":"Does LG1K065M7 include a circuit breaker?","answer":"No, the circuit breaker is ordered separately. The enclosure is designed to accept one, but it is not included with the LG1K065M7."},{"question":"Where to buy LG1K065M7?","answer":"The LG1K065M7 is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing — no stock figures or lead-time numbers are published for this obsolete part."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG1K065M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG1K065M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}