{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG1K065P705","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG1K065P705","canonicalUrl":"https://aoctrl.com/schneider/LG1K065P705","factsUrl":"https://aoctrl.com/api/mcp/products/LG1K065P705","rawCanonicalId":null},"summary":{"shortDescription":"TeSys LG, enclosed DOL starter, LG1K065P705, 0.63–1 A thermal protection, 230 V AC coil, IP55, AC-3 utilisation category.","salesMarkdown":"The TeSys LG1K065P705 is an enclosed DOL (direct-on-line) starter that packages a contactor, switch disconnector, and circuit-breaker into a single polycarbonate enclosure. It's rated for AC-3 duty — the standard motor-switching category per IEC 60947-4-1 — and its thermal protection adjustment range of 0.63 to 1 A sets the motor full-load current it can protect. That 0.63–1 A band covers small fractional-horsepower motors: 0.12 kW at 230 V AC, or 0.25 kW at 400/415 V AC. The 230 V AC control coil matches common plant control voltages in 50/60 Hz systems. The IP55 rating means the enclosure is dust-protected and can handle water jets from any direction — suitable for washdown areas or outdoor installations under cover. IK07 impact resistance adds a layer of mechanical toughness against accidental knocks. The push-button start/stop and rotary emergency stop on the front give local operator control without needing a separate control station. The 0.63–1 A thermal adjustment range must match the motor's full-load amperes; setting it too high defeats overload protection, too low causes nuisance trips. The 230 V AC coil voltage must match the control circuit supplying it — a 24 V DC system won't pull this in. Cable entries are 4 x Pg 13 plus 2 x Pg 16 on both top and bottom faces, giving flexibility for incoming supply and outgoing motor leads. The enclosure dimensions — 175 mm wide, 165 mm high, 165 mm deep — fit a standard panel footprint, but verify clearance for the rotary handle throw.","metaTitle":"TeSys LG1K065P705 Enclosed DOL Starter, 0.63–1 A, 230 V AC","metaDescription":"Obsolete TeSys LG1K065P705 enclosed DOL starter. 0.63–1 A thermal protection, 230 V AC coil, IP55, AC-3 duty. Sourced to order against RFQ via independent channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"165 mm","Range":"TeSys","Width":"175 mm","Height":"165 mm","Material":"Polycarbonate","Standards":"IEC 60204-1 IEC 60947-4-1","Control type":"Push-button start white I Push-button stop black O Rotary handle emergency stop red","Product name":"TeSys LG","Motor power kW":"0.12 kW at 220/230 V AC 50/60 Hz 0.25 kW at 400/415 V AC 50/60 Hz 0.25 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Device short name":"LG1K","Cable entry number":"4 2 Pg 13 + 2 Pg 16 top 4 2 Pg 13 + 2 Pg 16 bottom","Device application":"Safety","Device composition":"Contactor Switch disconnector Circuit-breaker","Utilisation category":"AC-3","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP55 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"230 V AC 50/60 Hz","Thermal protection adjustment range":"0.63...1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f3bd49652ad83f545eef4f78833e6e4e.pdf","sourceUrl":"https://www.se.com/be/en/product/LG1K065P705/tesys-lg-enclosed-dol-starter-0-63-1-a-230-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG1K065P705/alternatives.json"},"ai":{"faq":[{"question":"What replaces the LG1K065P705?","answer":"The manufacturer does not list a direct successor order code for this part. For a drop-in replacement, you would need to evaluate current enclosed DOL starters with the same thermal range (0.63–1 A), AC-3 rating, 230 V AC coil, and IP55 enclosure — no single pin-compatible alternative is documented."},{"question":"What compliance standards does the LG1K065P705 meet?","answer":"It complies with IEC 60204-1 (safety of machinery — electrical equipment) and IEC 60947-4-1 (contactors and motor-starters). Enclosure protection is IP55 per IEC 60529 and IK07 per IEC 60529 for impact resistance."},{"question":"Where can I buy the LG1K065P705?","answer":"We source this obsolete part through independent distribution channels. Submit an RFQ for current availability and pricing — each quote is confirmed at time of request against verified inventory."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG1K065P705","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG1K065P705 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}