{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG7K06E708","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG7K06E708","canonicalUrl":"https://aoctrl.com/schneider/LG7K06E708","factsUrl":"https://aoctrl.com/api/mcp/products/LG7K06E708","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LG, enclosed DOL starter, 2.5-4 A thermal protection, 48 V AC coil, IP55, IEC 60947-4-1.","salesMarkdown":"It is rated for AC-3 motor duty: 0.75 kW at 220/230 V AC and 1.5 kW at 400/415 V AC, with a thermal protection adjustment range of 2.5 to 4 A. The control circuit runs on 48 V AC, 50/60 Hz. The front panel has a white start push button, a black stop push button, and a red mushroom-head emergency stop, giving operators local control and a hard-wired E-stop without needing a separate station. ## Standards and compliance — what they certify This starter complies with IEC 60947-4-1 (the standard for contactors and motor-starters) and IEC 60204-1 (safety of machinery — electrical equipment). That means it is designed for the overcurrent, switching, and isolation duties a motor circuit demands, and it meets the machinery-safety requirements for emergency stop and control circuits. ## Integration — what it connects to and how it mounts Dimensions are 165 mm high, 175 mm wide, and 177 mm deep. The polycarbonate enclosure has four cable entries: two Pg 13 and two Pg 16 on the top, and the same on the bottom. That gives you multiple conduit or gland options for incoming and outgoing power and control wiring. It is an enclosed DOL starter, so it arrives as a single assembly — mount it directly to a wall, machine frame, or panel backplate. No separate enclosure or wiring of contactor to breaker is needed; the internal connections are factory-set.","metaTitle":"LG7K06E708 TeSys LG Enclosed DOL Starter, 2.5-4 A, 48 V AC","metaDescription":"TeSys LG7K06E708 enclosed DOL starter, 2.5-4 A thermal range, 48 V AC coil, IP55, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"177 mm","Range":"TeSys","Width":"175 mm","Height":"165 mm","Material":"Polycarbonate","Standards":"IEC 60947-4-1 IEC 60204-1","Control type":"Push-button start white I Push-button stop black O Mushroom head push-button emergency stop red","Product name":"TeSys LG","Motor power kW":"0.75 kW at 220/230 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Device short name":"LG7K","Cable entry number":"4 2 Pg 13 + 2 Pg 16 top 4 2 Pg 13 + 2 Pg 16 bottom","Device application":"Safety","Device composition":"Contactor Circuit-breaker","Utilisation category":"AC-3","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP55 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"48 V AC 50/60 Hz","Thermal protection adjustment range":"2.5...4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02bb149317768ac64869e4e153d7532d.pdf","sourceUrl":"https://www.se.com/uk/en/product/LG7K06E708/tesys-lg-enclosed-dol-starter-2-5-4-a-48-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG7K06E708/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LG7K06E708?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to LG7K06E708 in the TeSys family?","answer":"There is no official successor or direct pin-compatible alternative listed for this order code. The TeSys LG series includes other enclosed DOL starters with different thermal ranges and coil voltages; verify the thermal adjustment range (2.5-4 A) and control voltage (48 V AC) against any potential substitute."},{"question":"What compliance documentation does the brand provide for LG7K06E708?","answer":"The part is certified to IEC 60947-4-1 and IEC 60204-1. For RoHS, REACH, or UL documentation, the manufacturer typically provides declarations on request through the supply chain."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG7K06E708","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG7K06E708 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}