{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG7K06Q710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG7K06Q710","canonicalUrl":"https://aoctrl.com/schneider/LG7K06Q710","factsUrl":"https://aoctrl.com/api/mcp/products/LG7K06Q710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys LG enclosed DOL starter, LG7K06Q710, 4-6.3 A thermal protection, 380/400 V AC 50/60 Hz coil, IP55, includes contactor, circuit-breaker, emergency stop, two pushbuttons.","salesMarkdown":"The Schneider TeSys LG LG7K06Q710 is an enclosed direct-on-line (DOL) starter rated for AC-3 motor duty, combining a contactor and a circuit-breaker in a single IP55 polycarbonate enclosure with an integrated emergency stop and start/stop pushbuttons. Its thermal protection adjustment range of 4...6.3 A means the built-in overload relay is set to protect motors drawing full-load current in that band. The 380/400 V AC 50/60 Hz control coil matches standard European three-phase line voltages; at 440 V AC the starter handles a 3 kW motor, while at 400/415 V AC it delivers 2.2 kW and at 220/230 V AC it delivers 1.1 kW — so the same unit covers multiple supply voltages by derating the motor power. The IP55 polycarbonate enclosure (165 mm high, 175 mm wide, 177 mm deep) is rated for washdown environments and indoor industrial use where dust and water jets are present — think food processing, packaging lines, or pump stations that get hosed down. Cable entries are provided: 2 x Pg 13 and 2 x Pg 16 on both top and bottom faces, giving flexibility for top-entry or bottom-entry conduit runs without drilling the enclosure. ## Safety and compliance This starter is designed for safety applications per its device application listing, with a mushroom-head red emergency stop pushbutton that directly breaks the control circuit — meeting the stop category 0 requirement of IEC 60204-1. It complies with IEC 60204-1 (safety of machinery) and IEC 60947-4-1 (contactors and motor-starters), so it fits into CE-marked machinery control panels without additional coordination paperwork.","metaTitle":"Schneider LG7K06Q710 TeSys enclosed DOL starter, 4-6.3A","metaDescription":"Schneider TeSys LG7K06Q710 enclosed DOL starter. 4-6.3A thermal protection, IP55, 380/400V AC coil. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"177 mm","Range":"TeSys","Width":"175 mm","Height":"165 mm","Material":"Polycarbonate","Standards":"IEC 60204-1 IEC 60947-4-1","Control type":"Push-button start white I Push-button stop black O Mushroom head push-button emergency stop red","Product name":"TeSys LG","Motor power kW":"3 kW at 440 V AC 50/60 Hz 1.1 kW at 220/230 V AC 50/60 Hz 2.2 kW at 400/415 V AC 50/60 Hz","lifecycle_stage":"current","Device short name":"LG7K","Cable entry number":"4 2 Pg 13 + 2 Pg 16 top 4 2 Pg 13 + 2 Pg 16 bottom","Device application":"Safety","Device composition":"Contactor Circuit-breaker","Utilisation category":"AC-3","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP55 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"380/400 V AC 50/60 Hz","Thermal protection adjustment range":"4...6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c728e4048ce1f12de5988b89aba93d6.pdf","sourceUrl":"https://www.se.com/ie/en/product/LG7K06Q710/enclosed-dol-startertesys-lg46-3a380-400v-ac-coilincluding-1-lc1kgv2me-with-emergency-stop2-pushbuttons/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG7K06Q710/alternatives.json"},"ai":{"faq":[{"question":"Does LG7K06Q710 include a circuit breaker and thermal overload?","answer":"Yes, the unit includes a GV2ME circuit-breaker with an adjustable thermal overload relay (4...6.3 A range) and a contactor in one enclosure — no separate overload relay to wire in."},{"question":"What is the difference between LG7K06Q710 and LG7K06Q700?","answer":"The difference is the thermal protection adjustment range: the LG7K06Q710 covers 4...6.3 A, while the LG7K06Q700 covers a different range — check the specific overload setting needed for your motor's full-load current."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG7K06Q710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG7K06Q710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}