{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LG7K09S714","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LG7K09S714","canonicalUrl":"https://aoctrl.com/schneider/LG7K09S714","factsUrl":"https://aoctrl.com/api/mcp/products/LG7K09S714","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LG enclosed DOL starter, LG7K09S714, 6...10 A thermal protection, 500 V AC coil, IP55, IK07, AC-3, 4 kW at 400 V.","salesMarkdown":"The LG7K09S714 is a Schneider Electric TeSys LG enclosed direct-on-line (DOL) starter, combining a contactor and circuit-breaker in one IP55 polycarbonate enclosure. It's rated for AC-3 duty at 4 kW on a 400/415 V AC supply, with a thermal protection adjustment range of 6...10 A and a 500 V AC control coil. This is a safety-rated device per IEC 60947-4-1 and IEC 60204-1, with push-button controls including a white start, black stop, and red mushroom-head emergency stop. The thermal protection range of 6...10 A sets the overload relay trip window; you size the motor full-load current within that band. The 500 V AC coil means the control circuit must supply that voltage — not a standard 24 VDC or 230 V — so verify your panel's control transformer taps. Cable entry is generous: four Pg 13 and two Pg 16 knockouts on both top and bottom faces, giving flexibility for incoming supply and motor leads without extra gland plates. ## Deployment context This is a self-contained DOL starter for individual motor control — mount it on a wall, machine frame, or inside a panel. The polycarbonate enclosure is non-metallic, so no bonding earth lug is required for the enclosure itself, but the internal metal chassis must be earthed per IEC 60204-1. The push-button controls are integrated, so no separate start/stop station is needed for basic operation.","metaTitle":"LG7K09S714 TeSys LG Enclosed DOL Starter, 6...10 A, IP55, 50","metaDescription":"LG7K09S714 TeSys LG enclosed DOL starter. 4 kW at 400 V AC, AC-3, IP55, IK07. Active production. Order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"177 mm","Range":"TeSys","Width":"175 mm","Height":"165 mm","Material":"Polycarbonate","Standards":"IEC 60947-4-1 IEC 60204-1","Control type":"Push-button start white I Push-button stop black O Mushroom head push-button emergency stop red","Product name":"TeSys LG","Motor power kW":"4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 1.5 kW at 220/230 V AC 50/60 Hz","lifecycle_stage":"current","Device short name":"LG7K","Cable entry number":"4 2 Pg 13 + 2 Pg 16 top 4 2 Pg 13 + 2 Pg 16 bottom","Device application":"Safety","Device composition":"Contactor Circuit-breaker","Utilisation category":"AC-3","IK degree of protection":"IK07 conforming to IEC 60529","IP degree of protection":"IP55 conforming to IEC 60529","Product or component type":"Enclosed DOL starter","Environmental characteristic":"Standard environment","[Uc] control circuit voltage":"500 V AC 50/60 Hz","Thermal protection adjustment range":"6...10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/70bada7f37dd6e4bae75637a4251ff13.pdf","sourceUrl":"https://www.se.com/uk/en/product/LG7K09S714/tesys-lg-enclosed-dol-starter-6-10-a-500-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LG7K09S714/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LG7K09S714 and what is the lead time?","answer":"The LG7K09S714 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."},{"question":"What motor power does LG7K09S714 support?","answer":"It supports 4 kW at 400/415 V AC (50/60 Hz), 4 kW at 440 V AC, and 1.5 kW at 220/230 V AC, all in AC-3 duty."},{"question":"What is the closest alternative to LG7K09S714 in the TeSys range?","answer":"Within the TeSys LG family, the closest alternative would be a different thermal protection range variant — for example, a unit with a lower or higher adjustment window. The mechanical footprint and enclosure dimensions (177 mm depth, 175 mm width, 165 mm height) are shared across the LG7K series, so swapping within the range requires only verifying the overload setting matches the motor FLC."},{"question":"What compliance documentation does Schneider provide for LG7K09S714?","answer":"The LG7K09S714 is certified to IEC 60947-4-1 (low-voltage switchgear and controlgear for motor starters) and IEC 60204-1 (safety of machinery — electrical equipment). Standard documentation includes a CE declaration of conformity and the product datasheet. RoHS and REACH compliance is standard for the TeSys LG range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LG7K09S714","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LG7K09S714 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}