{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D40004ED","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D40004ED","canonicalUrl":"https://aoctrl.com/schneider/LP1D40004ED","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D40004ED","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, 4-pole contactor LP1D40004ED, AC-1 440 V 60 A, coil 48 V DC, rail/plate mount, IP2X.","salesMarkdown":"The Schneider Electric TeSys Deca LP1D40004ED is a 4-pole contactor rated for 60 A in AC-1 utilisation category at 440 V, with a 48 V DC coil. It is designed for resistive load switching in industrial control panels, where the AC-1 rating governs the continuous current-carrying capacity for non-inductive loads like heaters or lighting banks. The contactor is also listed for AC-3 and AC-3e duty. The 4-pole configuration (4P) means it can switch four independent circuits simultaneously, or be wired for two-pole switching with double-break per pole. Storage range extends from -60 to 80 °C. This covers most indoor industrial environments without special provisions. Mechanical robustness is specified for shock (10 Gn open, 15 Gn closed) and vibration (2 Gn open, 4 Gn closed, 5–300 Hz), which is typical for contactors mounted on machinery subject to moderate vibration. Mounting is on a rail or plate (the spec lists 'Rail Plate' as the mounting support). The dimensions are 85 mm wide, 127 mm high, and 182 mm deep — a standard footprint for the TeSys Deca 4-pole frame, so it fits existing panel layouts using that series. IP2X finger protection is provided, meaning the contactor is touch-safe when installed in an enclosure. The contactor is certified to IEC 60947-4-1, EN 60947-4-1, BS 5424, IEC 60947-1, EN 60947-1, JEM 1038, NF C 63-110, and VDE 0660 — covering the main international and European standards for contactors and motor-starters.","metaTitle":"TeSys LP1D40004ED 4-Pole Contactor, 60 A AC-1, 48 VDC Coil","metaDescription":"Active-production TeSys Deca contactor LP1D40004ED, 4 poles, rated 60 A AC-1 at 440 V, 48 VDC coil. IEC/EN 60947-4-1, UL 94 V-0. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"182 mm","Width":"85 mm","Height":"127 mm","Standards":"IEC 60947-4-1 EN 60947-4-1 BS 5424 IEC 60947-1 EN 60947-1 JEM 1038 NF C 63-110 VDE 0660","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting support":"Rail Plate","Non-overlap time":"1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts","Range of product":"TeSys Deca","Device short name":"LP1D","Poles description":"4P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1 AC-3 AC-3e AC-4","Contactor application":"Resistive load","Mechanical robustness":"Shocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)","IP degree of protection":"IP2X conforming to IEC 60529 IP2X conforming to VDE 0106","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-60...80 °C storage -40...60 °C operation 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/LP1D40004ED/contactor-tesys-lp1d-4-poles-ac1-440v-60-a-coil-48-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D40004ED/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a 4-pole contactor rated 60 A in AC-1 utilisation category at 440 V, with a 48 V DC coil. It is listed for AC-1, AC-3, AC-3e, and AC-4 duty. The non-overlap time between NC and NO contacts is 1.5 ms on both energisation and de-energisation."},{"question":"What mounting does it use?","answer":"Mounting support is rail or plate. Dimensions are 85 mm wide, 127 mm high, and 182 mm deep."},{"question":"What standards does it comply with?","answer":"It complies with IEC 60947-4-1, EN 60947-4-1, BS 5424, IEC 60947-1, EN 60947-1, JEM 1038, NF C 63-110, and VDE 0660. Fire resistance is 850 °C per IEC 60695-2-1, and the material is UL 94 V-1 rated."},{"question":"What is the ambient temperature range?","answer":"Operating range is -40 to 60 °C (with derating up to 70 °C). Storage range is -60 to 80 °C. Operation up to 3000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D40004ED","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D40004ED when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}