{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D40004JW","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D40004JW","canonicalUrl":"https://aoctrl.com/schneider/LP1D40004JW","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D40004JW","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca LP1D, 4-pole contactor, AC-1 60 A at 440 V, 12 V DC coil, IP2X, plate/rail mount.","salesMarkdown":"The Schneider Electric LP1D40004JW is a 4-pole contactor from the TeSys Deca family, rated for AC-1 60 A at 440 V with a 12 V DC coil. AC-1 covers resistive loads — heaters, lighting banks, non-inductive circuits — so the 60 A figure is the thermal current the main poles can carry continuously in that duty. For motor starting (AC-3), the switching capacity is lower; the utilisation category list includes AC-3 and AC-4, meaning this contactor is also specified for occasional motor switching, but the AC-1 number is the one that governs continuous current in a resistive circuit. Four poles give you the option to switch three phases plus a neutral, or two independent load circuits, in a single device. The 12 V DC coil draws from a control transformer or battery-backed supply — common in safety circuits or low-voltage control schemes where 24 V is the norm but 12 V legacy systems still run. Mounts on either a DIN rail or a mounting plate — the plate/rail support covers both panel-build styles. IP2X means finger-safe against accidental contact with live parts, which is the minimum for a panel-mounted device behind a locked door. Certified to IEC 60947-4-1 and EN 60947-4-1 (the contactor standard for motor starters and controllers), plus VDE 0660, JEM 1038, BS 5424, and NF C 63-110. That covers acceptance in European, Japanese, UK, and French markets. Operating temperature range is -40 to 60 °C, with derating above 60 °C up to 70 °C; storage from -60 to 80 °C.","metaTitle":"TeSys LP1D40004JW Contactor, 4P, AC-1 60A, 12 VDC Coil","metaDescription":"Schneider Electric TeSys Deca LP1D40004JW contactor, 4 poles, AC-1 60A at 440V, 12 VDC coil. Active production. Sourced to order. UL/CSA/IEC certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"182 mm","Width":"85 mm","Height":"127 mm","Standards":"VDE 0660 EN 60947-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1 JEM 1038 BS 5424 NF C 63-110","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting support":"Plate Rail","Non-overlap time":"1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts","Range of product":"TeSys Deca","Device short name":"LP1D","Poles description":"4P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1 AC-3 AC-3e AC-4","Contactor application":"Resistive load","Mechanical robustness":"Shocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)","IP degree of protection":"IP2X conforming to IEC 60529 IP2X conforming to VDE 0106","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-60...80 °C storage -40...60 °C operation 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/LP1D40004JW/contactor-tesys-lp1d-4-poles-ac1-440v-60-a-coil-12-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D40004JW/alternatives.json"},"ai":{"faq":[{"question":"What standards does the LP1D40004JW comply with?","answer":"It complies with IEC 60947-4-1, EN 60947-4-1, VDE 0660, JEM 1038, BS 5424, and NF C 63-110. Fire resistance is 850 °C per IEC 60695-2-1, and flame retardance is V1 per UL 94."},{"question":"What are the mounting options for this contactor?","answer":"It supports both plate and DIN-rail mounting. Dimensions are 85 mm wide, 127 mm high, and 182 mm deep."},{"question":"What is the ambient temperature range for operation?","answer":"Operating range is -40 to 60 °C, with derating allowed from 60 to 70 °C. Storage range is -60 to 80 °C. No derating is required up to 3000 m altitude."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D40004JW","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D40004JW when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}