{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D40004ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D40004ND","canonicalUrl":"https://aoctrl.com/schneider/LP1D40004ND","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D40004ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca LP1D40004ND, 4-pole contactor, AC-1 440V 60 A, coil 60 V DC, active production.","salesMarkdown":"The Schneider Electric LP1D40004ND is a 4-pole contactor from the TeSys Deca series, rated for 60 A in AC-1 utilisation category at 440 V, with a 60 VDC coil. The AC-1 rating means it is specified for resistive loads — heaters, lighting banks, or other non-inductive circuits — where the current inrush is minimal and the switching duty is steady-state. For motor loads, the AC-3 and AC-4 categories also listed on the device cover full-voltage starting and plugging/inching respectively. Mounts on a rail or plate per the mounting support spec. The IP2X finger protection (IEC 60529, VDE 0106) means the contactor is safe for open-panel installation where accidental contact is a concern, but not sealed against dust or moisture. ## What the standards tell you The contactor carries compliance with JEM 1038, EN 60947-1, VDE 0660, BS 5424, IEC 60947-1, EN 60947-4-1, NF C 63-110, and IEC 60947-4-1 — that covers the main global switching-device standards for industrial control gear. The IEC 60947-4-1 standard specifically governs contactors and motor-starters, so this part is accepted in panels destined for Europe, the UK, and markets that adopt IEC norms. Fire resistance at 850 °C (IEC 60695-2-1) and V-1 flame retardance (UL 94) on the housing materials mean it meets the flammability requirements for most industrial enclosures.","metaTitle":"TeSys LP1D40004ND contactor, 4-pole, 60 A AC-1, 60 VDC coil","metaDescription":"Schneider TeSys Deca LP1D40004ND 4-pole contactor rated 60 A AC-1 at 440 V, 60 VDC coil. Active production. UL/CSA/IEC. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"182 mm","Width":"85 mm","Height":"127 mm","Standards":"JEM 1038 EN 60947-1 VDE 0660 BS 5424 IEC 60947-1 EN 60947-4-1 NF C 63-110 IEC 60947-4-1","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting support":"Rail Plate","Non-overlap time":"1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts","Range of product":"TeSys Deca","Device short name":"LP1D","Poles description":"4P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1 AC-3 AC-3e AC-4","Contactor application":"Resistive load","Mechanical robustness":"Shocks contactor opened (10 Gn) Shocks contactor closed (15 gn) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)","IP degree of protection":"IP2X conforming to IEC 60529 IP2X conforming to VDE 0106","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-60...80 °C storage -40...60 °C operation 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/LP1D40004ND/contactor-tesys-lp1d-4-poles-ac1-440v-60-a-coil-60-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D40004ND/alternatives.json"},"ai":{"faq":[{"question":"What standards does the LP1D40004ND comply with?","answer":"It complies with JEM 1038, EN 60947-1, VDE 0660, BS 5424, IEC 60947-1, EN 60947-4-1, NF C 63-110, and IEC 60947-4-1. The housing is rated 850 °C fire resistance per IEC 60695-2-1 and V-1 flame retardance per UL 94."},{"question":"What are the physical dimensions of the LP1D40004ND?","answer":"The contactor measures 85 mm wide, 127 mm high, and 182 mm deep. It mounts on a rail or plate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D40004ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D40004ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}