{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D400086SW","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D400086SW","canonicalUrl":"https://aoctrl.com/schneider/LP1D400086SW","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D400086SW","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca LP1D400086SW, 4-pole contactor, 72 VDC wide-range coil, AC-1 resistive load rating, 182 mm depth.","salesMarkdown":"It is rated for AC-1 utilisation category, meaning it is designed for switching resistive loads — the rating that governs its thermal current capacity, not motor starting. The power circuit carries an average impedance of 1.5 mOhm at Ith 60 A, 50 Hz, and dissipates 5.4 W per pole under AC-1 load. Rated making and breaking capacity is 800 A at 440 V, per IEC 60947. Electrical durability is 1.4 million cycles at 60 A AC-1, Ue ≤ 440 V; mechanical durability is 10 million cycles. The contactor is rated for up to 3600 operating cycles per hour at 60 °C. The 72 VDC coil includes a built-in bidirectional peak limiting diode suppressor — no external flyback diode needed across the coil terminals. Inrush power is 22 W at 20 °C; the coil time constant is 75 ms. Opening time spans 4 to 19 ms, closing time 12 to 26 ms. Control circuit terminals accept lugs or ring terminals with an 8 mm outer diameter, torqued to 1.7 N·m on M3.5 screws (flathead or Philips No 2). ## Mounting, dimensions, and environment The contactor measures 85 mm wide, 127 mm high, and 182 mm deep. It mounts on a rail or plate. Fire resistance is 850 °C per IEC 60695-2-1; flame retardance is V1 per UL 94. Certified to CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 60947-4-1. The safety reliability level is expressed as B10d = 1,369,863 cycles with nominal load and B10d = 20,000,000 cycles with mechanical load, per EN/ISO 13849-1.","metaTitle":"Schneider Electric TeSys Deca LP1D400086SW Contactor, 72 VDC","metaDescription":"Schneider Electric TeSys Deca LP1D400086SW contactor, 4-pole, 72 VDC coil, AC-1 rated for resistive loads. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"182 mm","Range":"TeSys","Width":"85 mm","Height":"127 mm","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","Time constant":"75 ms","Operating time":"4...19 ms opening 12...26 ms closing","Coil technology":"Built-in bidirectional peak limiting diode suppressor","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting support":"Rail Plate","Pollution degree":"3","Protective cover":"Without","Range of product":"TeSys Deca","Average impedance":"1.5 mOhm - Ith 60 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W (at 20 °C)","Poles description":"4P","Tightening torque":"Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 6 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5","Compatibility code":"LP1D","Operating altitude":"0...3000 m","Control circuit type":"DC wide range","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"1.4 Mcycles 60 A AC-1 at Ue <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)","Associated fuse rating":"80 A gG at 80 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h at 60 °C","Connections - terminals":"Power circuit: lugs-ring terminals - external diameter: 16.5 mm Control circuit: lugs-ring terminals - external diameter: 8 mm","IP degree of protection":"IP20 front face conforming to IEC 60529","Rated breaking capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"5.4 W AC-1","[Uc] control circuit voltage":"72 V DC","[Ui] rated insulation voltage":"Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified","Control circuit voltage limits":"0.1...0.3 Uc (-40...70 °C):drop-out DC 0.75...1.2 Uc (-40...55 °C):operational DC 1...1.2 Uc (55...70 °C):operational DC","Hold-in power consumption in W":"22 W at 20 °C","[Ie] rated operational current":"60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 1000 V AC 25...400 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit 320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit","[Ith] conventional free air thermal current":"60 A (at 60 °C) for power circuit","Permissible ambient air temperature around the device":"-40...60 °C 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/63940d39ac27afc73e7861b4385e1030.pdf","sourceUrl":"https://www.se.com/uk/en/product/LP1D400086SW/tesys-d-contactor-4p2-no-+-2-nc-ac1-440-v-60-a-72-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D400086SW/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LP1D400086SW?","answer":"It is a 4-pole contactor with a 72 VDC wide-range coil, rated for AC-1 resistive loads. Electrical durability is 1.4 million cycles at 60 A AC-1, and mechanical durability is 10 million cycles."},{"question":"What compliance documentation is available for the LP1D400086SW?","answer":"The contactor is certified to CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 60947-4-1. It also carries a B10d safety reliability rating per EN/ISO 13849-1."},{"question":"What is the physical size of the LP1D400086SW?","answer":"The dimensions are 85 mm wide, 127 mm high, and 182 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D400086SW","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D400086SW when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}