{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D40008DW","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D40008DW","canonicalUrl":"https://aoctrl.com/schneider/LP1D40008DW","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D40008DW","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D, LP1D40008DW, 4-pole contactor, 60 A AC-1, 24 VDC coil, screw clamp terminals.","salesMarkdown":"The 24 VDC coil includes a built-in bidirectional peak limiting diode suppressor, so no external flyback diode is needed across the coil terminals; the suppressor is already in the package. The contactor carries a 1.4 Mcycle electrical durability at 60 A AC-1 under 440 V and a 10 Mcycle mechanical durability, which puts it in the standard-duty range for a panel that cycles several times per shift. This is a 4-pole contactor with a 2 NO + 2 NC pole contact composition, so it can switch two independent resistive loads or use the NC poles for auxiliary signalling in the same package. The control circuit terminals take up to 4 mm² and torque to 1.7 N·m. ## Standards and compliance — what the certifications mean for your panel The LP1D40008DW is certified to UL 508, CSA C22.2 No 14, IEC 60947-4-1, and IEC 60947-5-1. UL 508 covers industrial control equipment for the US market; CSA C22.2 No 14 is the Canadian counterpart. IEC 60947-4-1 is the standard for contactors and motor-starters, and IEC 60947-5-1 covers control-circuit devices and switching elements. The rated breaking capacity is 800 A at 440 V for the power circuit, conforming to IEC 60947. The associated fuse recommendation is 80 A gG at up to 690 V for coordination type 2, meaning with those fuses upstream, the contactor will survive a short circuit without damage and remain operational afterward. The maximum operating rate is 3600 cycles per hour at 60 °C, which is about one cycle per second — fast enough for most resistive load cycling applications but not for high-speed switching like a welding controller. The operating time is 4 to 19 ms for opening and 12 to 26 ms for closing. That is the mechanical travel time of the armature, not including the coil pickup delay. The inrush power at 20 °C is 22 W for the DC coil, and the average impedance of the power circuit is 1.5 mΩ at 60 A 50 Hz, which translates to about 5.4 W of heat dissipation in the power path at full rated current — negligible for panel thermal management but worth noting if the enclosure is tightly packed. ## Mechanical robustness and environmental limits The contactor is rated for vibration at 2 Gn (5 to 300 Hz) when open and 4 Gn when closed, and shock at 10 Gn for 11 ms when open and 15 Gn when closed. That is standard for industrial panel mounting — it will hold its contacts closed under moderate machine vibration but is not rated for direct mounting on a high-vibration source like a diesel engine without isolation. The operating altitude is up to 3000 m (9842 ft), which covers most installations except high-altitude mining or mountain-top sites above that threshold.","metaTitle":"Schneider Electric LP1D40008DW TeSys D Contactor, 4P, 60 A A","metaDescription":"Schneider Electric LP1D40008DW TeSys D contactor, 4-pole, 60 A AC-1 resistive rating, 24 VDC coil with built-in diode suppressor. UL/CSA/IEC certified, current production. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"7.2 in (182 mm)","Range":"TeSys","Width":"3.3 in (85 mm)","Height":"5 in (127 mm)","Category":"22357-CTR,TESYS D,OPEN,40-65A AC","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508","Time constant":"75 ms","Operating time":"4...19 ms opening 12...26 ms closing","Coil technology":"Built-in bidirectional peak limiting diode suppressor","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of Product":"TeSys D","Average impedance":"1.5 mOhm - Ith 60 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W 68 °F (20 °C))","Poles description":"4P","Tightening torque":"Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04...0.05 in² (25...35 mm²) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002...0.04 in² (1...25 mm²) hexagonal 0.2 in (4 mm)","Compatibility code":"LP1D","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"DC wide range","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"1.4 Mcycles 60 A AC-1 <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms)","Nbr. of units in pkg.":"1","Associated fuse rating":"80 A gG at 80 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h 140 °F (60 °C)","Connections - terminals":"Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: solid Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"5.4 W AC-1","[Uc] control circuit voltage":"96 V DC","[Ui] rated insulation voltage":"Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL","Control circuit voltage limits":"0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.75...1.2 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.2 Uc (131...158 °F (55...70 °C)):operational DC","Hold-in power consumption in W":"22 W 68 °F (20 °C)","[Ie] rated operational current":"60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit Power circuit <= 300 V DC","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947","[Icw] rated short-time withstand current":"72 A 104 °F (40 °C) - 10 min for power circuit 165 A 104 °F (40 °C) - 1 min for power circuit 320 A 104 °F (40 °C) - 10 s for power circuit 720 A 104 °F (40 °C) - 1 s for power circuit","[Ith] conventional free air thermal current":"60 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-76...176 °F (-60...80 °C) storage -40...140 °F (-40...60 °C) operation 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a679e8bedb6af7b5034c1cbf6a3759e9.pdf","sourceUrl":"https://www.se.com/uk/en/product/LP1D40008DW/tesys-d-contactor-4p2-no-+-2-nc-ac1-440-v-60-a-96-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D40008DW/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the LP1D40008DW in the TeSys D family?","answer":"The LP1D40008DW is a 4-pole contactor with a 24 VDC coil and a 60 A AC-1 rating. The closest alternative would be a TeSys D contactor with the same pole count and coil voltage but a different current rating, such as the LP1D40012DW for a 40 A AC-1 rating, or the LP1D40018DW for a 100 A AC-1 rating. The physical footprint and terminal layout are shared across the TeSys D range, so swapping between them typically requires only a rating check, not a panel rework."},{"question":"What is the depth of the LP1D40008DW?","answer":"The depth is 7.2 inches (182 mm). This is the dimension from the mounting surface to the furthest projection of the contactor body, not including any protruding terminals or wiring."},{"question":"What product range does the LP1D40008DW belong to?","answer":"It belongs to the TeSys D range from Schneider Electric. TeSys D is a series of contactors and motor starters designed for industrial control panels, covering currents from about 9 A to 150 A in AC-3 duty and higher in AC-1."},{"question":"What compliance documentation is available for the LP1D40008DW?","answer":"The contactor is certified to UL 508, CSA C22.2 No 14, IEC 60947-4-1, and IEC 60947-5-1. It also carries a pollution degree 3 rating, fire resistance tested to 850 °C per IEC 60695-2-1, and flame retardance V1 per UL 94. RoHS and REACH compliance documentation is standard for Schneider Electric TeSys D products, though specific declarations should be requested with the order if required for your compliance file."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D40008DW","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D40008DW when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}