{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D40008PD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D40008PD","canonicalUrl":"https://aoctrl.com/schneider/LP1D40008PD","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D40008PD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D LP1D40008PD, 4-pole contactor, 40-65A DC coil, AC-1 rated for resistive loads, 800 A breaking capacity at 440 V.","salesMarkdown":"It carries a DC standard control circuit with a built-in bidirectional peak limiting diode suppressor for coil suppression. The contactor is rated for a 40-65A DC coil and is intended for panel-mount or DIN-rail installation. Rated for AC-1 duty, this contactor is specified for resistive loads — think heater banks, lighting, or non-inductive circuits — not for motor starting. The associated fuse recommendation of 80 A gG at <= 690 V (coordination type 2) tells you the upstream protection needed to keep the contactor operational after a short circuit. The 4-pole configuration (2 NO + 2 NC) gives flexibility for switching multiple circuits or implementing interlocking. Mechanical durability of 10 Mcycles and electrical durability of 1.4 Mcycles at 60 A AC-1 <= 440 V indicate a long service life under rated conditions. Tightening torque for the power circuit is 70.8 lbf.in (8 N.m); control circuit is 15.05 lbf.in (1.7 N.m). The operating time (4...19 ms opening, 12...26 ms closing) and maximum operating rate of 3600 cycles per hour at 60 °C define the switching speed and duty cycle limits for the application.","metaTitle":"Schneider Electric LP1D40008PD TeSys D Contactor, 4P, 40-65A","metaDescription":"Schneider Electric TeSys D LP1D40008PD 4-pole contactor, 40-65A DC coil, AC-1 rated, 800A breaking capacity at 440V. UL/CSA/IEC listed. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"7.2 in (182 mm)","Range":"TeSys","Width":"3.3 in (85 mm)","title":"LP1D40008PD","Height":"5 in (127 mm)","Category":"22358-CTR,TESYS D,OPEN,40-65A DC","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508","description":"TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 60 A - 155 V DC coil","Time constant":"75 ms","Operating time":"4...19 ms opening 12...26 ms closing","Coil technology":"Built-in bidirectional peak limiting diode suppressor","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of Product":"TeSys D","Average impedance":"1.5 mOhm - Ith 60 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W 68 °F (20 °C))","Poles description":"4P","Tightening torque":"Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04...0.05 in² (25...35 mm²) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002...0.04 in² (1...25 mm²) hexagonal 0.2 in (4 mm)","Compatibility code":"LP1D","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"DC DC standard","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"1.4 Mcycles 60 A AC-1 <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms)","Nbr. of units in pkg.":"1","Associated fuse rating":"80 A gG at 80 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h 140 °F (60 °C)","Connections - terminals":"Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: solid Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"5.4 W AC-1","[Uc] control circuit voltage":"155 V DC","[Ui] rated insulation voltage":"Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL","Control circuit voltage limits":"0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.1 Uc (131...158 °F (55...70 °C)):operational DC","Hold-in power consumption in W":"22 W 68 °F (20 °C)","[Ie] rated operational current":"60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit Power circuit <= 300 V DC","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947","[Icw] rated short-time withstand current":"72 A 104 °F (40 °C) - 10 min for power circuit 165 A 104 °F (40 °C) - 1 min for power circuit 320 A 104 °F (40 °C) - 10 s for power circuit 720 A 104 °F (40 °C) - 1 s for power circuit","[Ith] conventional free air thermal current":"60 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-76...176 °F (-60...80 °C) storage -40...140 °F (-40...60 °C) operation 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07c0751abc8391283584406b27c9bd7d.pdf","sourceUrl":"https://www.se.com/ie/en/product/LP1D40008PD/tesys-d-contactor-4p2-no-+-2-nc-ac1-440-v-60-a-155-v-dc-coil/"},"ai":{"faq":[{"question":"What are the key ratings of the LP1D40008PD?","answer":"It is a 4-pole contactor rated for AC-1 (resistive load) duty, with a DC standard control circuit (40-65A DC coil). Breaking capacity is 800 A at 440 V. Mechanical durability is 10 Mcycles; electrical durability is 1.4 Mcycles at 60 A AC-1 <= 440 V."},{"question":"What compliance documentation does the LP1D40008PD carry?","answer":"It is listed under CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 508. Flame retardance is V1 per UL 94; fire resistance is 850 °C per IEC 60695-2-1."},{"question":"What is the depth of the LP1D40008PD?","answer":"The depth is 7.2 in (182 mm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D40008PD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D40008PD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}