{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D80004BD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D80004BD","canonicalUrl":"https://aoctrl.com/schneider/LP1D80004BD","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D80004BD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys Deca LP1D80004BD 4-pole DC coil contactor, 125 A AC-1 resistive load, with protective cover.","salesMarkdown":"If your BOM requires motor switching (AC-3 or AC-4), this contactor is not the correct fit; the AC-1 rating caps the making and breaking current for resistive duty only. ## Coil and control The coil is DC control circuit type rated at 22 W inrush at 68 °F (20 °C). There is no built-in suppressor module fitted, so plan an external flyback diode across the coil if the driving output is a solid-state relay or PLC transistor output. Operating time is 6...20 ms opening and 20...35 ms closing. Tighten control circuit terminals to 10.6 lbf·in (1.2 N·m). Dimensions: 7.1 in (181 mm) depth, 3.8 in (96 mm) width, 5 in (127 mm) height. Compliant with UL 60947-4-1, CSA C22.2 No 14, EN 60947-4-1, and IEC 60947-4-1. Flame retardance V1 per UL 94, fire resistance at 1562 °F (850 °C).","metaTitle":"Schneider LP1D80004BD TeSys Deca Contactor, 4P DC Coil, AC-1","metaDescription":"LP1D80004BD TeSys Deca 4-pole DC coil contactor, rated 125 A AC-1 for resistive loads. In active production. Complies with IEC/UL 60947. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"7.1 in (181 mm)","Range":"TeSys","Width":"3.8 in (96 mm)","Height":"5 in (127 mm)","Category":"US10I1222359","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","Time constant":"75 ms","Operating time":"6...20 ms opening 20...35 ms closing","Coil technology":"Without built-in suppressor module","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Rail Plate","Pollution degree":"3","Protective cover":"With","Range of Product":"TeSys Deca","Average impedance":"0.8 mOhm - Ith 125 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W 68 °F (20 °C))","Poles description":"4P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm) Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals pozidriv No 2","Compatibility code":"LP1D","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"DC DC standard","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"0.8 Mcycles 125 A AC-1 <= 440 V","Mechanical durability":"4 Mcycles","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms)","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h at 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: flexible without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible with cable end Power circuit: connector 2 0.006...0.02 in² (4...16 mm²) - cable stiffness: flexible with cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: solid Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"12.5 W AC-1 5.1 W AC-3 5.1 W AC-3e","[Uc] control circuit voltage":"24 V DC","[Ui] rated insulation voltage":"Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1","Control circuit voltage limits":"0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.1 Uc (131...158 °F (55...70 °C)):operational DC","Hold-in power consumption in W":"22 W 68 °F (20 °C)","[Ie] rated operational current":"125 A (at 80 A (at 80 A (at 55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit","[Ue] rated operational voltage":"Power circuit Power circuit <= 300 V DC","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947","[Icw] rated short-time withstand current":"135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit","[Ith] conventional free air thermal current":"125 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$179.62","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/61ca7b6a99ad61becf9f44529bbe4f2c.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D80004BD/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of LP1D80004BD?","answer":"Depth is 7.1 in (181 mm)."},{"question":"What standards does LP1D80004BD comply with?","answer":"It complies with CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 60947-4-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D80004BD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D80004BD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}