{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D80004MD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D80004MD","canonicalUrl":"https://aoctrl.com/schneider/LP1D80004MD","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D80004MD","rawCanonicalId":null},"summary":{"shortDescription":"TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 125 A - 220 V DC coil","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"7.1 in (181 mm)","Range":"TeSys","Width":"3.8 in (96 mm)","Height":"5 in (127 mm)","Category":"22359-CTR,TESYS D,OPEN,80-150A AC&DC","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508","Time constant":"75 ms","Operating time":"6...20 ms opening 20...35 ms closing","Coil technology":"Without built-in suppressor module","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of Product":"TeSys Deca","Average impedance":"0.8 mOhm - Ith 125 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W 68 °F (20 °C))","Poles description":"4P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)","Compatibility code":"LP1D","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"DC DC standard","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"0.8 Mcycles 125 A AC-1 <= 440 V","Mechanical durability":"4 Mcycles","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms)","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h at 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: flexible without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible with cable end Power circuit: connector 2 0.006...0.02 in² (4...16 mm²) - cable stiffness: flexible with cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: solid Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"12.5 W AC-1","[Uc] control circuit voltage":"220 V DC","[Ui] rated insulation voltage":"Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1","Control circuit voltage limits":"0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.1 Uc (131...158 °F (55...70 °C)):operational DC","Hold-in power consumption in W":"22 W 68 °F (20 °C)","[Ie] rated operational current":"125 A (at 80 A (at 80 A (at 55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit","[Ue] rated operational voltage":"Power circuit Power circuit <= 300 V DC","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947","[Icw] rated short-time withstand current":"135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit","[Ith] conventional free air thermal current":"125 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c207998cb33e40999b50706694ae9cc2.pdf","sourceUrl":"https://www.se.com/uk/en/product/LP1D80004MD/tesys-d-contactor-4p4-no-ac1-440-v-125-a-220-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D80004MD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D80004MD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D80004MD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}