{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1D80008ED","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1D80008ED","canonicalUrl":"https://aoctrl.com/schneider/LP1D80008ED","factsUrl":"https://aoctrl.com/api/mcp/products/LP1D80008ED","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, TeSys Deca series, 4-pole contactor LP1D80008ED, rated 125 A in AC-1, screw-clamp control and power terminals, current active production.","salesMarkdown":"The LP1D80008ED: The 125 A AC-1 figure is the load current you can switch continuously — that is the headroom for resistive heaters, lighting banks, or transformer primaries. Making and breaking capacity at 440 V is 1100 A, so it handles inrush from cold resistive elements without welding contacts. Mechanical durability is 10 Mcycles; the electrical durability of 0.8 Mcycles at rated load tells you the contact wear life under continuous use. Mounts on either plate or rail (DIN). IP20 front face. Power circuit terminals accept 4 to 50 mm² (flexible without end sleeve), control circuit screw clamps take 1 to 4 mm². Torque for power terminals is 12 N·m — a standard screwdriver or hex driver. Depth is 196 mm (7.7 in), width 96 mm, height 127 mm, so it fits a standard 300 mm deep enclosure on a backplate. Operating altitude up to 3000 m; no derating needed at most altitudes.","metaTitle":"Schneider LP1D80008ED TeSys Deca Contactor, 125 A AC-1, 4-po","metaDescription":"Active production. 4-pole TeSys Deca contactor rated 125 A in AC-1 duty for resistive loads. UL, CSA, IEC 60947 certified. Depth 7.7 in. Order with confidence for BOM fill.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"7.7 in (196 mm)","Range":"TeSys","Width":"3.8 in (96 mm)","Height":"5 in (127 mm)","Category":"US10I1222359","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","Time constant":"75 ms","Operating time":"6...20 ms opening 20...35 ms closing","Coil technology":"Without built-in suppressor module","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of Product":"TeSys Deca","Average impedance":"0.8 mOhm - Ith 125 A 50 Hz for power circuit","Device short name":"LP1D","Inrush power in W":"22 W 68 °F (20 °C))","Poles description":"4P","Tightening torque":"Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm) Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2","Compatibility code":"LP1D","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"DC DC standard","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"0.8 Mcycles 125 A AC-1 <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms)","Nbr. of units in pkg.":"1","Associated fuse rating":"200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h at 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: flexible without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible with cable end Power circuit: connector 2 0.006...0.02 in² (4...16 mm²) - cable stiffness: flexible with cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: solid Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"12.5 W AC-1","[Uc] control circuit voltage":"48 V DC","[Ui] rated insulation voltage":"Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1","Control circuit voltage limits":"0.1...0.3 Uc (-40...131 °F (-40...55 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC","Hold-in power consumption in W":"22 W 68 °F (20 °C)","[Ie] rated operational current":"125 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit <= 690 V AC 25...400 Hz","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947","[Icw] rated short-time withstand current":"135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit","[Ith] conventional free air thermal current":"125 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$800.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/61ca7b6a99ad61becf9f44529bbe4f2c.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1D80008ED/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available?","answer":"UL 60947-4-1, CSA C22.2 No 14, IEC 60947-4-1, and IEC 60947-5-1. Fire resistance rated at 850 °C (IEC 60695-2-1) and flame retardance V1 per UL 94."},{"question":"What are the key dimensions?","answer":"Depth 7.7 in (196 mm), width 3.8 in (96 mm), height 5 in (127 mm)."},{"question":"What is the range or series of this contactor?","answer":"TeSys Deca, the heavy-duty industrial contactor family from Schneider Electric."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1D80008ED","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1D80008ED when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}