{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1K12004JD3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1K12004JD3","canonicalUrl":"https://aoctrl.com/schneider/LP1K12004JD3","factsUrl":"https://aoctrl.com/api/mcp/products/LP1K12004JD3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, LP1K12004JD3, 4P (4 NO), AC-1 rated 20 A at ≤440 V, 12 V DC coil, 57 mm depth.","salesMarkdown":"For motor loads (AC-3 duty), this unit is not rated — select a TeSys K variant with AC-3 utilisation category instead. The 4 NO pole configuration gives four independent switching paths, all closing on coil energisation, suited for three-phase plus neutral or four independent resistive circuits. Rated breaking capacity reaches 110 A at 440 V, 80 A at 500 V, and 70 A at 660…690 V per IEC 60947, so it interrupts fault currents well above its continuous rating. The rated making capacity is 144 A AC for the power circuit. Impulse withstand voltage is 8 kV (Uimp), and insulation voltage (Ui) is 690 V per IEC 60947-4-1, 600 V per UL 508 and CSA C22.2 No 14. Coil operating limits are 0.8…1.15 Uc for pick-up and 0.1…0.75 Uc for drop-out at under 50 °C. Operating time is 30…40 ms for coil energisation and NO closing, 10 ms for de-energisation and NO opening. Maximum operating rate is 3600 cycles per hour. Mechanical durability is 10 million cycles. For safety applications, B10d is 1,369,863 cycles with nominal load and 20,000,000 cycles with mechanical load per EN/ISO 13849-1.","metaTitle":"Schneider TeSys K LP1K12004JD3 Contactor, 4P 4NO, 20A AC-1,","metaDescription":"Schneider TeSys K LP1K12004JD3 contactor, 4P 4NO, 20A AC-1 at 690V, 12V DC coil. Active production. UL/CSA/IEC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1","Operating time":"30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening","Coil technology":"Built-in bidirectional peak limiting diode suppressor","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Mounting support":"Plate Rail","Range of product":"TeSys K","Average impedance":"3 mOhm - Ith 20 A 50 Hz for power circuit","Device short name":"LP1K","Inrush power in W":"3 W (at 20 °C)","Poles description":"4P","Tightening torque":"1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm","Compatibility code":"LP1K","Operating altitude":"2000 m without derating","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"25 A gG at 25 A aM for power circuit","Maximum operating rate":"3600 cyc/h","Rated breaking capacity":"110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947","Pole contact composition":"4 NO","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"144 A AC for power circuit conforming to NF C 63-110 144 A AC for power circuit conforming to IEC 60947","[Ui] rated insulation voltage":"Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14","Control circuit voltage limits":"Operational: 0.8...1.15 Uc (at Drop-out: 0.1...0.75 Uc (at <50 °C)","Hold-in power consumption in W":"3 W at 20 °C","[Ie] rated operational current":"20 A (at 16 A (at <70 °C) at 690 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Ith] conventional free air thermal current":"20 A (at 50 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9c3614fe13c185595a2baff874d5d5f.pdf","sourceUrl":"https://www.se.com/ie/en/product/LP1K12004JD3/tesys-k-contactor-4p-4-no-ac1-440v-20a-12v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1K12004JD3/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The critical ratings are: 4 poles (4 NO), AC-1 utilisation category, 20 A rated operational current at 690 V AC, 12 V DC coil with operating limits of 0.8…1.15 Uc pick-up and 0.1…0.75 Uc drop-out. Dimensions are 45 x 58 x 57 mm for DIN-rail or plate mounting."},{"question":"What compliance documentation is available?","answer":"The contactor is certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. The manufacturer provides RoHS, REACH, and UL/CSA/IEC compliance documentation upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1K12004JD3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1K12004JD3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}