{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1K12004ND","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1K12004ND","canonicalUrl":"https://aoctrl.com/schneider/LP1K12004ND","factsUrl":"https://aoctrl.com/api/mcp/products/LP1K12004ND","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 4P (4 NO), AC-1 rated 20 A at ≤440 V, 60 V DC coil, screw-clamp terminals.","salesMarkdown":"Its conventional free-air thermal current (Ith) is 20 A at 50 °C for the power circuit, and the rated operational current (Ie) is 20 A at 690 V AC, 50/60 Hz. That AC-1 rating means it handles resistive loads like heaters or lighting banks at full rated current without derating for motor inrush; for motor duty (AC-3) you would need a different rating. The coil is 60 V DC, with an operating range of 0.8 to 1.15 times the control voltage and a drop-out band of 0.1 to 0.75 Uc below 50 °C. Inrush power at 20 °C is 3 W; hold-in power is also 3 W — a continuous-duty coil, not a power-saver design. Screw-clamp terminals accept a Philips No 2 or flat 6 mm screwdriver at 1.3 N·m tightening torque. The 4-pole, all-NO configuration means it switches four independent resistive circuits simultaneously; no auxiliary contacts are integrated, so add a separate block if you need a feedback signal. ## Approvals and standards Certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Overvoltage category III, rated impulse withstand voltage 8 kV. Flame retardance meets UL 94 V1 and NF F 16-101/102 requirements. These approvals cover most industrial control panels in North America, Europe, and Asia.","metaTitle":"Schneider Electric LP1K12004ND TeSys K Contactor, 4P 4NO, 20","metaDescription":"Active-production TeSys K contactor, 4P 4NO, rated 20 A AC-1 at 690 V. 60 VDC coil, screw terminals. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","title":"LP1K12004ND","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1","description":"TeSys K contactor, 4P (4 NO),AC-1, <= 440V, 20A, 60V DC coil","Operating time":"30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Mounting support":"Rail Plate","Range of product":"TeSys K","Average impedance":"3 mOhm - Ith 20 A 50 Hz for power circuit","Device short name":"LP1K","Inrush power in W":"3 W (at 20 °C)","Poles description":"4P","Tightening torque":"1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm","Compatibility code":"LP1K","Operating altitude":"2000 m without derating","Overvoltage category":"III","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"25 A gG at 25 A aM for power circuit","Maximum operating rate":"3600 cyc/h","Rated breaking capacity":"110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947","Pole contact composition":"4 NO","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"144 A AC for power circuit conforming to NF C 63-110 144 A AC for power circuit conforming to IEC 60947","[Ui] rated insulation voltage":"Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14","Control circuit voltage limits":"Operational: 0.8...1.15 Uc (at Drop-out: 0.1...0.75 Uc (at <50 °C)","Hold-in power consumption in W":"3 W at 20 °C","[Ie] rated operational current":"20 A (at 16 A (at <70 °C) at 690 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Ith] conventional free air thermal current":"20 A (at 50 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/274046c2c423ea9a7a4fe29e1adfe823.pdf","sourceUrl":"https://www.se.com/nl/en/product/LP1K12004ND/tesys-k-contactor-4p-4-no-ac1-440v-20a-60v-dc-coil/"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current (Ie) is 20 A in AC-1 at 690 V AC; conventional free-air thermal current (Ith) is 20 A at 50 °C. Coil is 60 V DC. It has 4 poles, all normally open."},{"question":"What compliance documentation is available for the LP1K12004ND?","answer":"The contactor carries approvals to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. It also meets UL 94 V1 flame retardance and NF F 16-101/102 requirements."},{"question":"What is the physical size of the LP1K12004ND?","answer":"45 mm wide, 58 mm high, 57 mm deep. It mounts on a DIN rail or plate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1K12004ND","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1K12004ND when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}