{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1K12015FD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1K12015FD","canonicalUrl":"https://aoctrl.com/schneider/LP1K12015FD","factsUrl":"https://aoctrl.com/api/mcp/products/LP1K12015FD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3P, AC-3 <=440V, 12A, 1 NC aux, 110V DC coil, obsolete.","salesMarkdown":"The LP1K12015FD is a TeSys K three-pole contactor from Schneider Electric, rated 12 A in AC-3 utilisation category at up to 440 V, with a 110 V DC coil and one normally closed auxiliary contact. It is listed as obsolete, so this is a last-time-buy or surplus-sourcing part — not something you'd spec into a new panel design. The 12 A AC-3 rating governs motor switching up to that current — that's the number that decides whether it handles your load, not the higher AC-1 resistive rating. Coil hold-in power is 3 W at 20 °C, which matters for control transformer sizing and thermal budget inside the enclosure. The 110 V DC coil is less common than 24 VDC or 230 VAC; verify your control voltage matches before committing the BOM line. Flame retardance meets V1 per UL 94 and also complies with NF F 16-101 and NF F 16-102 — relevant if the panel must pass rail or transit fire-safety standards. ## Sourcing reality Schneider has marked this contactor obsolete. No official successor order code appears in the record, so there is no direct drop-in replacement from the manufacturer. If you're filling a BOM for an existing panel, confirm the coil voltage and aux contact arrangement match; if you're designing new, look at current TeSys K or TeSys D catalog numbers with a 110 VDC coil option. ## Physical integration The 3 NO pole contact composition with 1 NC aux is a common configuration for direct-on-line motor starters. Spring-cage or screw terminals depending on variant; verify termination type on the nameplate before panel wiring.","metaTitle":"Schneider TeSys K LP1K12015FD Contactor, 12A AC-3, 110V DC C","metaDescription":"Obsolete TeSys K contactor, 3P, AC-3 <=440V, 12A, 1 NC aux, 110V DC coil. Sourced to order against RFQ. Depth 57 mm, width 45 mm, height 58 mm.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Range of product":"TeSys K","Device short name":"LP1K","Inrush power in W":"3 W (at 20 °C)","Poles description":"3P","Compatibility code":"LP1K","Utilisation category":"AC-3 AC-1 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","Hold-in power consumption in W":"3 W at 20 °C","[Ie] rated operational current":"20 A (at 12 A at 16 A (at 10 MOhm for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/769c03f681c556a750bcab14be297805.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP1K12015FD/tesys-k-contactor-3p-ac3-440v-12a-1-nc-aux-110v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1K12015FD/alternatives.json"},"ai":{"faq":[{"question":"What replaces the LP1K12015FD?","answer":"No official successor order code is recorded. For a new design, select a current TeSys K or TeSys D contactor with a 110 VDC coil and matching pole/aux configuration. For an existing BOM, verify the coil voltage and aux contact arrangement before ordering a substitute."},{"question":"What are the key ratings for the LP1K12015FD?","answer":"Rated 12 A in AC-3 (motor switching) at up to 440 V, with a 110 V DC coil. Coil hold-in power is 3 W at 20 °C. Three normally open main poles and one normally closed auxiliary contact."},{"question":"What compliance documentation does the LP1K12015FD carry?","answer":"Flame retardance rated V1 per UL 94, and also compliant with NF F 16-101 and NF F 16-102 for rail/transit applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1K12015FD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1K12015FD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}