{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP1SK0600CD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP1SK0600CD","canonicalUrl":"https://aoctrl.com/schneider/LP1SK0600CD","factsUrl":"https://aoctrl.com/api/mcp/products/LP1SK0600CD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys SK series, LP1SK0600CD mini contactor, 2-pole (2 NO), AC-1 rated 12 A at 690 V, 36 V DC coil, DIN rail mount.","salesMarkdown":"The 36 V DC coil draws 2.2 W hold-in power, so verify your control transformer can supply that continuously — it's a standard DC control voltage, common in 24-48 VDC panels. This is a mini contactor, not a full-frame power contactor — the 27 mm width and 56 mm height let it fit tight DIN-rail enclosures where panel space is at a premium. The 55.5 mm depth keeps it clear of gland plates in shallow backboxes. Mounts on standard DIN rail. Power circuit wiring accepts 0.35 to 6 mm² solid or flexible cable — spring-cage or screw terminals, depending on the connector variant. The 0.8 N.m tightening torque on the connector is light; a Pozidriv No. 1 driver is the tool. Two cables per terminal are allowed for daisy-chaining, but only up to 1.5 mm² flexible with ferrules — keep that in mind when looping through multiple contactors. IP2X finger protection per VDE 0106 means the live parts are guarded against accidental contact, but it's not sealed — no washdown rating. Keep it inside the enclosure. Certified to EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 — the contactor standard for motor starters and switching. The associated fuse rating is 16 A gI at ≤ 440 V for the power circuit, so coordinate your branch circuit protection accordingly.","metaTitle":"Schneider TeSys LP1SK0600CD Mini Contactor, 2P NO, 12A AC-1,","metaDescription":"Schneider TeSys SK LP1SK0600CD mini contactor, 2-pole NO, 12A AC-1 resistive load, 36 V DC coil. Current production. DIN rail mount. IEC/UL/CSA certified. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"55.5 mm","Range":"TeSys","Width":"27 mm","Height":"56 mm","Standards":"EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"4...6 ms coil de-energisation and NO opening 8...12 ms coil energisation and NO closing","lifecycle_stage":"current","Heat dissipation":"2.2 W","Mounting support":"Rail","Average impedance":"4 mOhm - Ith 12 A 50 Hz","Device short name":"LP1SK","Inrush power in W":"2.2 W (at 20 °C)","Tightening torque":"0.8 N.m - on connector - with screwdriver pozidriv No 1","Operating altitude":"2000 m without derating","Control circuit type":"DC standard","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50015","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"16 A gI at <= 440 V for power circuit conforming to IEC 60947","Maximum operating rate":"1200 cyc/h","Connections - terminals":"Power circuit: connector 1 cable(s) 0.35...6 mm²flexible with cable end Power circuit: connector 1 cable(s) 0.5...6 mm²flexible without cable end Power circuit: connector 1 cable(s) 1.5...6 mm²solid Power circuit: connector 2 cable(s) 0.35...1.5 mm²flexible with cable end Power circuit: connector 2 cable(s) 0.35...2.5 mm²flexible without cable end Power circuit: connector 2 cable(s) 1.5...4 mm²solid","IP degree of protection":"IP2X conforming to VDE 0106","Rated breaking capacity":"52 A at 52 A at <= 400 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO","Product or component type":"Mini contactor","Irms rated making capacity":"66 A at 690 V AC conforming to IEC 60947 66 A at 690 V AC conforming to NF C 63-110","[Uc] control circuit voltage":"36 V DC","[Ui] rated insulation voltage":"690 V conforming to IEC 60947 690 V conforming to VDE 0110 group C 690 V conforming to BS 5424 690 V conforming to UL 508 690 V conforming to CSA C22.2 No 14","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at Drop-out: 0.1...0.75 Uc (at <50 °C)","Hold-in power consumption in W":"2.2 W at 20 °C","Power Pole Contact Composition":"2P","[Ie] rated operational current":"12 A (at <55 °C) AC AC-1","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz","Ambient air temperature for storage":"-50...70 °C","Ambient air temperature for operation":"-20...50 °C","[Icw] rated short-time withstand current":"50 A 55 °C for power circuit","[Ith] conventional free air thermal current":"12 A (at 55 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f103ee2de87cf4f2a247cc5a6c9af026.pdf","sourceUrl":"https://www.se.com/be/en/product/LP1SK0600CD/tesys-sk-mini-contactor-2p-2-no-ac1-690-v-12-a-36-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP1SK0600CD/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current (Ie) is 12 A at 690 V AC under AC-1 (resistive load). The coil is 36 V DC, drawing 2.2 W hold-in power. Mechanical durability is 10 million cycles, and the maximum operating rate is 1200 cycles per hour."},{"question":"What compliance documentation does Schneider provide for this part?","answer":"The part carries IEC, UL, and CSA certifications per EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. The rated insulation voltage is 690 V per those standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP1SK0600CD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP1SK0600CD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}