{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K06013BD3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K06013BD3","canonicalUrl":"https://aoctrl.com/schneider/LP2K06013BD3","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K06013BD3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LP2K06013BD3, 3P, AC-3 ≤440 V 6 A, 1 NC, 24 V DC coil, IP20.","salesMarkdown":"The LP2K06013BD3 is a TeSys K reversing contactor from Schneider Electric — a preassembled 3-pole unit with an integral reversing power busbar, rated for AC-3 motor duty at 6 A up to 440 V and AC-4 duty for inching/jogging applications. The 24 V DC coil and one normally-closed auxiliary contact are built in; the contactor carries an IP20 finger-safe enclosure per VDE 0106, so it mounts in a standard control panel without additional shrouding on the terminals. This part is listed as Obsolete by the manufacturer. The TeSys K series has been superseded by the TeSys Deca range in most applications, but pin-to-pin compatibility depends on the mounting footprint and coil voltage; verify the panel layout before substituting. Rated operational voltage on the power circuit is 690 V AC 50/60 Hz, though the AC-3 motor rating is specified at ≤440 V. The contactor handles vibration up to 4 Gn closed (5–300 Hz per IEC 60068-2-6) and shock at 15 Gn closed on the Z axis — figures that matter for mobile or skid-mounted equipment. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is typical for rail and transit panel specs.","metaTitle":"Schneider Electric LP2K06013BD3 TeSys K Reversing Contactor,","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 6 A at 440 V, 24 VDC coil, 1 NC. Sourced to order against RFQ. IP20, 57 mm depth.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"57 mm","Width":"90 mm","Height":"58 mm","IP Rating":"IP20","Application":"Motor control","Product Status":"Active","Temp Storage Max":"80 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...80 °C","Utilization Category":"AC-4 AC-3","Main Product Or Component Type":"Reversing contactor","Ambient Air Temperature Operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cd95eb138b8af2bc02d5e664f642c79d.pdf","sourceUrl":"https://www.se.com/vn/en/product/LP2K06013BD3/tesys-k-reversing-contactor-3p-ac3-440-v-6-a-1-nc-24-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP2K06013BD3/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K06013BD3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K06013BD3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}