{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K06105FD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K06105FD","canonicalUrl":"https://aoctrl.com/schneider/LP2K06105FD","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K06105FD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 6 A, 1 NO, 110 V DC coil, IP20, V1 flame retardance.","salesMarkdown":"It carries 3 NO power poles rated for AC-3 duty up to 6 A at 440 V, and AC-4 switching capability for inching and plugging applications. The AC-3 rating of 6 A at 440 V governs motor switching — that's the current the contactor can make and break across a standard squirrel-cage induction motor load. The AC-4 rating covers the more severe duty of reversing and plugging, where the contactor interrupts locked-rotor current. The 690 V AC rated operational voltage on the power circuit gives headroom for 480 V or 575 V systems, but the motor current rating at those voltages will be lower than the 440 V figure — always size by the AC-3 current at your line voltage. The 110 V DC coil draws steady DC, so verify your control supply can source the inrush without droop; DC coils don't have the same holding-current drop as AC coils. The LP2K06105FD measures 90 mm wide by 58 mm high by 57 mm deep, with IP20 finger-safe protection per VDE 0106. It's designed for DIN-rail mounting inside an enclosure. The V1 flame-retardance rating per UL 94 means the housing won't propagate a flame — important for panel layouts where multiple contactors are ganged. Operating altitude is 2000 m without derating; above that, the air density drop reduces the contactor's interrupting capacity.","metaTitle":"TeSys K LP2K06105FD Reversing Contactor, 3P, 6A AC-3, 110 VD","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 <=440 V 6 A, 1 NO, 110 V DC coil. Sourced to order against RFQ. IP20, V1 flame retardance.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d9f9b0cfa11a3de0adeb0b3dc1863f8a.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP2K06105FD/tesys-k-reversing-contactor-3p-ac3-440-v-6-a-1-no-110-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP2K06105FD/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LP2K06105FD?","answer":"It is a 3-pole reversing contactor rated for AC-3 duty at 6 A up to 440 V, with a 110 V DC coil. The power circuit is rated for 690 V AC. It carries IP20 protection and V1 flame retardance per UL 94."},{"question":"How do I source the LP2K06105FD?","answer":"Submit an RFQ with your quantity and target price. Because the part is obsolete, we source it from surplus and broker channels — no factory lead time applies."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K06105FD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K06105FD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}