{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K0901KD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K0901KD","canonicalUrl":"https://aoctrl.com/schneider/LP2K0901KD","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K0901KD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 9 A, 1 NC, 100 V DC coil, IP20, 57 x 90 x 58 mm.","salesMarkdown":"Its headline rating: AC-3 duty at ≤440 V, 9 A, with a 100 V DC coil. The 9 A figure at 440 V tells you the motor FLA it can handle; for a 400 V line, that typically covers a 3–4 kW motor, depending on the duty cycle. The contactor also carries AC-4 and AC-1 utilisation categories, so it can manage inching/plugging (AC-4) and resistive loads (AC-1) within its thermal current limits. The power circuit is rated for 690 V AC 50/60 Hz, giving headroom for 480 V or 575 V systems, though the AC-3 current rating derates above 440 V — check the thermal curve for higher voltages. The contactor is IP20 rated (finger-safe terminals per VDE 0106), so it's intended for enclosure or panel mounting — not exposed washdown areas. The preassembled reversing busbar saves panel wiring time, but verify the busbar orientation matches your reversing starter layout before committing the panel. The coil is 100 V DC, so it needs a DC supply or a rectified AC source. The contactor includes one NC auxiliary contact (the '01' in the code), which is typically used for electrical interlocking in the reversing circuit — a standard practice to prevent both contactors from closing simultaneously.","metaTitle":"Schneider Electric LP2K0901KD TeSys K Reversing Contactor, 9","metaDescription":"Obsolete Schneider TeSys K reversing contactor, 3P, AC-3 9A at 440V, 100 VDC coil, IP20. Sourced to order against RFQ. LP2K0901KD.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4c353d05e2de5dad32e8dd221bba8fea.pdf","sourceUrl":"https://www.se.com/sg/en/product/LP2K0901KD/tesys-k-reversing-contactor-3p-ac3-440-v-9-a-1-nc-100-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP2K0901KD/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LP2K0901KD?","answer":"It is a 3-pole reversing contactor rated AC-3 at ≤440 V, 9 A, with a 100 V DC coil. It also covers AC-4 and AC-1 categories. The power circuit is rated for 690 V AC 50/60 Hz. It includes one NC auxiliary contact."},{"question":"What is the physical size of the LP2K0901KD?","answer":"The dimensions are 57 mm deep, 90 mm wide, and 58 mm tall. It has an IP20 protection rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K0901KD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K0901KD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}