{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K12004MPD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K12004MPD","canonicalUrl":"https://aoctrl.com/schneider/LP2K12004MPD","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K12004MPD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K LP2K12004MPD, 4-pole changeover contactor, 230 V DC control, 20 A AC-1, preassembled with reversing power busbar.","salesMarkdown":"The 230 V DC coil pulls in at 0.8 to 1.15 times rated voltage and drops out between 0.1 and 0.75 Uc, which gives a clean pick-up margin even on a sagging DC bus. Rated 20 A in AC-1 utilisation category (resistive load), it handles the full thermal current of the power circuit at 50 Hz with an average impedance of 3 mOhm. Breaking capacity is 110 A at 440 V, 80 A at 500 V, and 70 A at 660 to 690 V, all per IEC 60947 — so it can interrupt a fault without welding contacts, which matters when you're swapping a motor that's locked rotor. Screw-clamp terminals accept one or two solid conductors from 1.5 to 4 mm², or flexible with ferrules from 0.34 to 2.5 mm². Tightening torque is 1.3 N·m with a No. 2 Phillips or a 6 mm flat-blade screwdriver. IP20 finger protection per VDE 0106, so it's safe inside a locked panel but not for open-panel washdown areas. Operating altitude is 2000 m without derating; above that you'll need to reduce current or increase clearance. The 20 A AC-1 rating is the continuous resistive load it can switch. For motor loads, you'd use the AC-3 rating (not listed here), which is lower — this contactor is designed for resistive or lightly inductive control circuits, not direct motor starting. The 3 W heat dissipation at 20 °C means it won't cook adjacent components in a crowded panel, but the inrush power is also 3 W at 20 °C, so the coil hold-in power is the same as the pull-in — a DC coil with no AC hum. Mechanical durability is 5 million cycles; electrical durability is 300,000 cycles at 20 A AC-1 at up to 440 V. Maximum operating rate is 3600 cycles per hour — one per second — which is fast enough for rapid reversing in a conveyor or transfer table. The B10d safety reliability figures are 1,369,863 cycles at nominal load and 20 million cycles at mechanical load per EN/ISO 13849-1, so it's usable in safety-related control circuits up to that statistical life.","metaTitle":"Schneider Electric TeSys K LP2K12004MPD Changeover Contactor","metaDescription":"Schneider Electric TeSys K LP2K12004MPD changeover contactor, 4 poles, 230 VDC control coil. Rated 20 A AC-1, breaking capacity 110 A at 440 V. Current production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LP2K12004MPD","Height":"58 mm","Standards":"VDE 0660 NF C 63-110 IEC 60947 BS 5424","description":"TeSys K changeover contactor, 4P, AC,1 <= 440 V 20 A, 230 V DC coil","Product name":"TeSys K","Operating time":"30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"3 W","Mounting support":"Plate Rail","Average impedance":"3 mOhm - Ith 20 A 50 Hz for power circuit","Device short name":"LP2K","Inrush power in W":"3 W (at 20 °C)","Interlocking type":"Mechanical","Poles description":"4P","Tightening torque":"1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Control circuit type":"DC standard","Overvoltage category":"III","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"0.3 Mcycles 20 A AC-1 at Ue <= 440 V","Mechanical durability":"5 Mcycles","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","Associated fuse rating":"25 A gG at 25 A aM for power circuit","Maximum operating rate":"3600 cyc/h","Connections - terminals":"Screw clamp terminals 1 cable(s) 1.5...4 mm²solid Screw clamp terminals 1 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34...2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1.5...4 mm²solid Screw clamp terminals 2 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.34...1.5 mm²flexible with cable end","IP degree of protection":"IP20 conforming to VDE 0106","Rated breaking capacity":"110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Changeover contactor","Irms rated making capacity":"144 A AC for power circuit conforming to NF C 63-110 144 A AC for power circuit conforming to IEC 60947","[Uc] control circuit voltage":"230 V DC","[Ui] rated insulation voltage":"Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14","Control circuit voltage limits":"Operational: 0.8...1.15 Uc (at Drop-out: 0.1...0.75 Uc (at <50 °C)","Hold-in power consumption in W":"3 W at 20 °C","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"20 A (at 16 A (at <70 °C) at 690 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"115 A 50 °C - 1 s for power circuit 105 A 50 °C - 5 s for power circuit 100 A 50 °C - 10 s for power circuit 75 A 50 °C - 30 s for power circuit 55 A 50 °C - 1 min for power circuit 50 A 50 °C - 3 min for power circuit 25 A 50 °C - >= 15 min for power circuit","[Ith] conventional free air thermal current":"20 A (at 50 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/21e6af0f6cc7ccf6a7e5b91783d9361a.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP2K12004MPD/tesys-k-changeover-contactor-4p-ac1-440-v-20-a-230-v-dc-coil/"},"ai":{"faq":[{"question":"What is the control voltage for this contactor?","answer":"The control circuit voltage is 230 V DC. The coil operates between 0.8 and 1.15 times Uc for pick-up, and drops out between 0.1 and 0.75 Uc at temperatures below 50 °C."},{"question":"What breaking capacity does it have?","answer":"Rated breaking capacity is 110 A at 440 V, 80 A at 500 V, and 70 A at 660 to 690 V, all per IEC 60947. This lets it safely interrupt fault currents up to those levels."},{"question":"What compliance documentation is available?","answer":"The contactor complies with IEC 60947-4-1, VDE 0660, NF C 63-110, BS 5424, UL 508, and CSA C22.2 No 14. It carries V1 flame retardance per UL 94 and meets railway standards NF F 16-101 and NF F 16-102."},{"question":"What is the physical size of this contactor?","answer":"Dimensions are 90 mm wide, 58 mm high, and 57 mm deep. The 57 mm depth is the critical clearance dimension for enclosure door clearance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K12004MPD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K12004MPD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}