{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K1210CD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K1210CD","canonicalUrl":"https://aoctrl.com/schneider/LP2K1210CD","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K1210CD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NO auxiliary, 36 V DC coil, preassembled with reversing power busbar.","salesMarkdown":"## Integration and mechanical fit The contactor measures 90 mm wide × 58 mm high × 57 mm deep, with IP20 finger-safe protection per VDE 0106 — suitable for enclosed panel mounting where accidental contact is a concern. It's rated for operation at -25 to 50 °C ambient and up to 2000 m altitude without derating. The V1 flame-retardance rating per UL 94 and NF F 16-101/102 matters for rail and transit applications where fire-smoke-toxicity compliance is required. Mechanical shock and vibration ratings (15 Gn closed, 10 Gn open on Z axis) confirm it holds in high-vibration environments like compressor skids or mobile equipment.","metaTitle":"Schneider TeSys K LP2K1210CD Reversing Contactor, 12A AC-3,","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 ≤440V 12A, 1 NO, 36V DC coil. Sourced to order against RFQ. IP20 finger-safe, preassembled reversing busbar.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9740a4c03084015ab48f001fd1aa6156.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP2K1210CD/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-no-36-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP2K1210CD/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for fit?","answer":"AC-3 motor-switching current is 12 A at ≤440 V, with a 36 V DC coil. The contactor is 3-pole with 1 NO auxiliary contact, preassembled with the reversing busbar. Rated operational voltage is 690 V AC 50/60 Hz on the power circuit."},{"question":"What compliance documentation is available?","answer":"The contactor carries IP20 per VDE 0106, V1 flame retardance per UL 94, and meets NF F 16-101/102 for rail fire-smoke-toxicity. Mechanical robustness is qualified to IEC 60068-2-27 (shock) and IEC 60068-2-6 (vibration)."},{"question":"How do I source this obsolete part?","answer":"It is quoted to order against an RFQ through surplus and broker inventory. No direct replacement order code is listed by Schneider, so verify the coil voltage and reversing busbar arrangement match your existing design before ordering."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K1210CD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K1210CD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}