{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K1210GD3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K1210GD3","canonicalUrl":"https://aoctrl.com/schneider/LP2K1210GD3","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K1210GD3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LP2K1210GD3, 3P, AC-3 <= 440 V 12 A, 1 NO, 125 V DC coil, IP20.","salesMarkdown":"The AC-4 and AC-1 utilisation categories are also covered, giving flexibility for inching/jogging or resistive loads. The 690 V AC rated operational voltage on the power circuit gives headroom for 480 V or 575 V systems, but the AC-3 current derates above 440 V; check the thermal curve if running at the higher voltage. The 125 V DC coil is less common than 24 VDC or 120 VAC — verify your control supply matches before committing the BOM line. ## Mechanical and environmental robustness Rated to withstand 15 Gn shock for 11 ms with contacts closed (IEC 60068-2-27) and 4 Gn vibration at 5–300 Hz closed — figures that matter for applications mounted on machinery or in mobile equipment where mechanical shock is a concern. The flame retardance meets V1 per UL 94 and NF F 16-101, which is relevant for rail and transport applications that require strict fire-smoke-toxicity compliance. Operating altitude is 2000 m without derating, so it is fine for most installations outside high-altitude sites. The preassembled reversing busbar saves panel-build time — no loose bus links to torque or lose. The 125 V DC coil is polarity-sensitive; verify the free-wheel diode or suppression module is correctly oriented if the control circuit uses DC switching.","metaTitle":"Schneider Electric TeSys K LP2K1210GD3 Reversing Contactor,","metaDescription":"TeSys K reversing contactor LP2K1210GD3, 3P, AC-3 <= 440 V 12 A, 1 NO, 125 V DC coil. Active production. IP20. Preassembled with reversing busbar. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LP2K1210GD3","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 12 A, 1 NO, 125 V DC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Resistive load Motor control","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa8820ca00a0e84ebb228612f0cf9d64.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP2K1210GD3/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-no-125-v-dc-coil/"},"ai":{"faq":[{"question":"What are the key ratings for the LP2K1210GD3?","answer":"It is a 3-pole reversing contactor rated for AC-3 duty at 12 A up to 440 V, with a 125 V DC coil. The power circuit is rated for 690 V AC 50/60 Hz, and it also covers AC-4 and AC-1 utilisation categories."},{"question":"What is the physical size of the LP2K1210GD3?","answer":"Dimensions are 90 mm wide, 58 mm high, and 57 mm deep."},{"question":"What compliance documentation is available for the LP2K1210GD3?","answer":"The contactor carries V1 flame retardance per UL 94, and meets NF F 16-101 and NF F 16-102 requirements for rail applications. It also conforms to IEC 60068 for shock and vibration, and VDE 0106 for IP20 protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K1210GD3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K1210GD3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}