{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K1210JD3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K1210JD3","canonicalUrl":"https://aoctrl.com/schneider/LP2K1210JD3","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K1210JD3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LP2K1210JD3, 3P, AC-3 ≤ 440 V 12 A, 1 NO auxiliary contact, 12 V DC coil, preassembled with reversing power busbar.","salesMarkdown":"The Schneider Electric LP2K1210JD3 is a TeSys K reversing contactor — a compact 3-pole unit rated for 12 A in AC-3 duty at up to 440 V, with a 12 V DC coil and one normally-open auxiliary contact built in. The AC-3 rating of 12 A at ≤ 440 V means it handles the inrush and switching of a standard three-phase squirrel-cage induction motor up to roughly 5.5 kW at 400 V — the typical load for a small conveyor, pump, or fan. It also carries AC-1 (resistive) and AC-4 (plugging/reversing) utilisation categories, so it's rated for the full duty cycle of reversing applications, not just steady-state running. The 12 V DC coil pulls in reliably at the nominal voltage. Verify the coil suppression matches your PLC output card's sink current; a free-wheeling diode across the coil is standard practice to protect the output transistor from the inductive kick. Rated for ambient operation from -25 °C to 50 °C and storage from -50 °C to 80 °C, with no derating up to 2000 m altitude. The V1 flame-retardance rating per UL 94 means the housing material self-extinguishes — a standard requirement for panel-mounted control gear.","metaTitle":"Schneider TeSys K LP2K1210JD3 reversing contactor, 12 A AC-3","metaDescription":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 12 A, 1 NO auxiliary, 12 V DC coil. Active production. IP20. Preassembled reversing busbar. UL 94 V1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LP2K1210JD3","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 12 A, 1 NO, 12 V DC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3 AC-1","Contactor application":"Resistive load Motor control","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1aaed41c7f349ef28ea9856bd2148eb0.pdf","sourceUrl":"https://www.se.com/in/en/product/LP2K1210JD3/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-no-12-v-dc-coil/"},"ai":{"faq":[{"question":"What are the key ratings for this reversing contactor?","answer":"It is a 3-pole reversing contactor rated 12 A in AC-3 duty at ≤ 440 V, with a 12 V DC coil and one NO auxiliary contact. The power circuit is rated for 690 V AC 50/60 Hz. It covers AC-1, AC-3, and AC-4 utilisation categories."},{"question":"What compliance documentation is available for the LP2K1210JD3?","answer":"The housing carries a V1 flame-retardance rating per UL 94, and the IP20 protection is per VDE 0106. The protective treatment conforms to IEC 60068 and DIN 50016. Standard Schneider declarations for RoHS and REACH apply to the TeSys K range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K1210JD3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K1210JD3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}