{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP2K1210UD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP2K1210UD","canonicalUrl":"https://aoctrl.com/schneider/LP2K1210UD","factsUrl":"https://aoctrl.com/api/mcp/products/LP2K1210UD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NO, 250 V DC coil, IP20, active production.","salesMarkdown":"The LP2K1210UD is a TeSys K reversing contactor — 3 poles, 3 NO power contacts, preassembled with the reversing power busbar so it's ready to drop into a motor-reversing circuit without extra wiring. Its AC-3 rating of 12 A at ≤440 V is the number that governs motor switching: that's the current under starting and plugging duty, not the resistive AC-1 figure, so it directly sizes the contactor for a reversing motor starter up to that load. The coil is 250 V DC, which means the contactor pulls in on a DC control circuit — common in battery-backed or industrial DC control panels. Rated operational voltage on the power circuit goes to 690 V AC 50/60 Hz, giving headroom if the line voltage steps up. Ambient operating range is -25 to 50 °C, so it's fine in most ventilated enclosures but derate above 50 °C. For a BOM line that calls out LP2K1210UD, the fit is confirmed by the AC-3 12 A motor-switching rating and the 250 VDC coil. No pin-compatible direct alternative exists within the same series at this exact rating — the LP2K series is organized by coil voltage and current; the 12 A AC-3 with 250 VDC coil is a specific intersection. If the coil voltage is wrong, the whole contactor must change.","metaTitle":"Schneider Electric LP2K1210UD TeSys K Reversing Contactor, 1","metaDescription":"Active-production reversing contactor, AC-3 rated 12 A at ≤440 V, 3P NO, 250 VDC coil, IP20, flame retardance V1. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LP2K1210UD","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 12 A, 1 NO, 250 V DC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LP2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4 AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f94021e7fec1f8cc71d20f598ea4965c.pdf","sourceUrl":"https://www.se.com/mk/en/product/LP2K1210UD/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-no-250-v-dc-coil/"},"ai":{"faq":[{"question":"What is the closest alternative in the TeSys K family if LP2K1210UD is not available?","answer":"Within the same TeSys K reversing contactor family, the LP2K series is organized by rated operational current and coil voltage. The 12 A AC-3 rating paired with a 250 VDC coil is a specific variant; the nearest sibling would share the same current rating and poles but differ in coil voltage. Changing coil voltage means rewiring the control circuit, so verify the existing panel's DC supply before substituting."},{"question":"What is the depth of LP2K1210UD?","answer":"The depth is 57 mm, which is the dimension from the DIN-rail mounting plane to the front of the contactor body."},{"question":"What compliance documentation is available for LP2K1210UD?","answer":"The contactor carries IP20 protection per VDE 0106, flame retardance V1 per UL 94, and meets NF F 16-101 and NF F 16-102 Requirement 2 for rail rolling stock. Protective treatment is TC per IEC 60068 and DIN 50016 for damp-heat cyclic testing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP2K1210UD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP2K1210UD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}