{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP4K06013BW3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP4K06013BW3","canonicalUrl":"https://aoctrl.com/schneider/LP4K06013BW3","factsUrl":"https://aoctrl.com/api/mcp/products/LP4K06013BW3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3P, AC-3/AC-3e 440V 6A, 1NC aux, 24V DC low consumption coil, spring terminals.","salesMarkdown":"The 1 NC auxiliary contact is built in, saving a separate aux block for basic feedback or interlocking. Rated operational voltage for the power circuit is 440 V, and the control circuit holds in from 0.7 to 1.3 times Uc (the rated control voltage) at 20 °C, dropping out reliably at 0.1 Uc below 50 °C. That gives you a solid 16.8 V to 31.2 V window on a 24 V nominal coil — forgiving on a sagging DC bus during a multi-contactor pickup. No screwdriver torque check, no loose strands — just strip 8 mm and push. Saves time on a rail full of contactors. IP2X finger protection on the front means it's safe for open-panel builds behind a locked door, but it's not washdown-rated; keep it in a dry cabinet. Ambient temperature range of -25 °C to 50 °C covers most plant-floor conditions; storage from -50 °C to 80 °C handles warehouse extremes. Global approvals are already in place: UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC 60947-4-1, plus GB/T 14048.4 for China. Flame retardance meets UL 94 V1 and NF F 16-101/102. No separate certification wait for most markets. Electrical durability at that load is 1.3 million cycles, and mechanical durability hits 30 million cycles, so it outlasts most machines in light-duty conveyor or pump service. Maximum operating rate is 3600 cycles per hour, fine for repetitive pick-and-place or valve sequencing. Coil inrush and hold-in power are both 1.8 W at 20 °C — that's the heat you need to budget in a sealed enclosure. Operating time: 10 to 20 ms to open the NO contacts on coil drop, 30 to 40 ms to close on energisation. Fast enough for safety interlocks when paired with a proper safety relay. Minimum switching capability for the signalling circuit is 5 mA at 17 V — so the NC aux can reliably wet a PLC input or a small relay without contact oxidation issues at low currents. Safety reliability is quantified: B10d of 1,369,863 cycles under nominal load per EN/ISO 13849-1, and 20 million cycles under mechanical load. That's useful for a risk assessment on a guard-monitoring contactor.","metaTitle":"Schneider Electric TeSys K LP4K06013BW3 Contactor, 6A AC-3,","metaDescription":"Active 3-pole contactor from TeSys K series. Rated 6A AC-3/AC-3e at 440V. 24V DC low-consumption coil with integral suppression. 1 NC aux contact. Spring terminals. UL/CSA/IEC cert","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","title":"LP4K06013BW3","Height":"58 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4","description":"Contactor, TeSys K, 3P, AC-3/AC-3e, 440V, 6A, 1NC aux, 24V DC low consumption coil,spring terminal","Operating time":"10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing","Coil technology":"With integral suppression device","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.8 W","Mounting support":"Plate Rail","Device short name":"LP4K","Inrush power in W":"1.8 W (at 20 °C)","Poles description":"3P","Operating altitude":"2000 m without derating","Utilisation category":"AC-3 AC-3e AC-4","Contactor application":"Motor control","Electrical durability":"1.3 Mcycles 6 A AC-3 at Ue 1.3 Mcycles 6 A AC-3e at Ue 0.05 Mcycles 36 A AC-4 at Ue <= 440 V","Mechanical durability":"30 Mcycles","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NC","Connections - terminals":"Spring terminals 1 cable(s) 0.75...1.5 mm²solid Spring terminals 1 cable(s) 0.75...1.5 mm²flexible without cable end Spring terminals 2 cable(s) 0.75...1.5 mm²flexible without cable end","IP degree of protection":"IP2X","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Control circuit voltage limits":"Operational: 0.7...1.3 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)","Hold-in power consumption in W":"1.8 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$45.05 – $60.43","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/095086d8936fc4ad60156b2bbba1aa68.pdf","sourceUrl":"https://www.se.com/vn/en/product/LP4K06013BW3/contactor-tesys-k-3p-ac3-ac3e-440v-6a-1nc-aux-24v-dc-low-consumption-coilspring-terminal/"},"ai":{"faq":[{"question":"What is the closest alternative to LP4K06013BW3 in the TeSys K family?","answer":"Within the same TeSys K range, the LP4K06013BW3 is a 3-pole, 6 A AC-3 contactor with a 24 V DC low-consumption coil and spring terminals. A direct pin-compatible alternative would be the same order code — there is no electrically identical variant with a different coil voltage or terminal type that shares the same footprint. If you need a 24 V DC coil but with screw terminals, that would be a different order code (e.g., LP4K06013BW3 is spring; the screw-terminal version carries a different suffix). Check the TeSys K catalog for the screw-terminal variant if wiring preference differs."},{"question":"What compliance documentation is available for LP4K06013BW3?","answer":"The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and GB/T 14048.4. Flame retardance meets UL 94 V1 and NF F 16-101/102. RoHS and REACH declarations are typically provided by Schneider Electric on request for this active catalog part."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP4K06013BW3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP4K06013BW3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}