{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LP5K12004BW3","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LP5K12004BW3","canonicalUrl":"https://aoctrl.com/schneider/LP5K12004BW3","factsUrl":"https://aoctrl.com/api/mcp/products/LP5K12004BW3","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K LP5K12004BW3 changeover contactor, 4-pole, 24 V DC coil, preassembled with reversing power busbar, screw clamp terminals, IP20.","salesMarkdown":"Rated for AC-1 resistive load duty, it breaks 110 A at 440 V and makes 144 A AC, with a rated insulation voltage of 690 V per IEC 60947-4-1 and 600 V per UL 508. The built-in bidirectional peak limiting diode suppressor handles coil suppression internally — no external flyback diode needed on the DC control circuit. The 24 V DC control circuit operates between 0.7 and 1.30 Uc (roughly 16.8 to 31.2 V DC) and drops out between 0.1 and 0.7 Uc, so it holds in during brownout conditions down to about 17 V but releases reliably below 7 V. Mechanical durability is rated at 5 million cycles, with electrical durability of 300,000 cycles at 20 A AC-1 at up to 440 V — the mechanical life is the limit for dry switching or very light loads. The screw clamp terminals accept 1 to 2 conductors from 0.34 to 4 mm² (solid or flexible with/without ferrule), torqued to 0.8–1.3 N·m — standard for panel wiring with a No. 2 Phillips or 6 mm flat driver. Mechanical interlocking is built in, preventing simultaneous closure of both contactors in a reversing pair — no external interlock relay needed.","metaTitle":"Schneider Electric LP5K12004BW3 TeSys K Changeover Contactor","metaDescription":"Schneider Electric LP5K12004BW3 TeSys K changeover contactor, 4-pole, 24 V DC coil, preassembled reversing busbar. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"57 mm","Width":"90 mm","Height":"58 mm","Current":"20 A (at 16 A (at <70 °C) at 690 V AC AC-1 for power circuit","Voltage":"Power circuit: <= 690 V AC 50/60 Hz","IP Rating":"IP20","Application":"Resistive load","Coil Voltage":"24 V DC","Operating Time":"10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing","Product Status":"Active","Temp Storage Max":"80 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947","Temp Operating Max":"50 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...80 °C","Control Circuit Type":"DC low consumption","Utilization Category":"AC-1","Electrical Life Cycles":"0.3 Mcycles 20 A AC-1 at Ue <= 440 V","Mechanical Life Cycles":"5 Mcycles","Main Product Or Component Type":"Changeover contactor","Ambient Air Temperature Operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc8c8ee524380f194500e3f31e2afaa8.pdf","sourceUrl":"https://www.se.com/be/en/product/LP5K12004BW3/tesys-k-changeover-contactor-4p-ac1-440-v-20-a-24-v-dc-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LP5K12004BW3/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LP5K12004BW3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LP5K12004BW3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}