{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LTMTEFM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LTMTEFM","canonicalUrl":"https://aoctrl.com/schneider/LTMTEFM","factsUrl":"https://aoctrl.com/api/mcp/products/LTMTEFM","rawCanonicalId":null},"summary":{"shortDescription":"Motor Management main unit, TeSys Tera, EtherNet IP/Modbus TCP, 4 DI and 3 DO, supply 100-240VAC/DC","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Overload Relays"],"specifications":{"Depth":"3.5 in (90 mm)","Range":"TeSys","Width":"4.4 in (112 mm)","Height":"1.8 in (45 mm)","Bus type":"Ethernet IEEE 802.3 0...159 10...100 Mbit/s, 2xRJ45 4 shielding pairs cable","Category":"US10I1222335","Standards":"EN/IEC 60947-4-1 UL/CSA 60947-4-1","Load current":"10 A 250 V AC/DC 5 A 30 V DC","Product name":"TeSys Tera","Web services":"Web server","Input current":"3 mA 100...240 V","Metering type":"Thermal memory Line, phase and average current Line to line and average voltage Motor temperature input Ground fault current Ig Active and reactive power Active and reactive energy Frequency Total voltage harmonic distortion THD (V) Total voltage harmonic distortion THD (U) Total current harmonic distortion THD (I) Phase sequence","Fire resistance":"1202 °F (650 °C) IEC 60947-1 1760 °F (960 °C) UL 94","Protection Type":"Overload protection Stalled rotor Locked rotor Short-circuit Undercurrent Overcurrent Current unbalance Phase reversal Phase loss Earth fault protection internal Earth fault protection external Excessive starting time Max number of start Undervoltage Overvoltage Voltage unbalance Underfrequency Overfrequency Reacceleration Temperature protection Analog input protection Communication failure Fail to stop Under power Over power Power factor variation Anti-backspin timer Block output DI interlock protection","lifecycle_stage":"unknown","Connection pitch":"0.3 in (7.5 mm) for supply voltage 0.2 in (5.0 mm) for others","Pollution degree":"3","Device short name":"LTMT","Permissible power":"480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)","Device Application":"Equipment monitoring and control","Logic input number":"4","Operating altitude":"<= 6561.68 ft (2000 m) without derating","Current Consumption":"8...62.8 mA","Measurement accuracy":"1 % current 0.3...3 A) 1 % current 2.5...25 A) 3 % current 7...70 A) 3 % current 10...100 A) 1 % voltage 110...690 V) +/- 2.5 % earth fault current external measurement +/- 3...5 % earth fault current internal measurement current > 0.03 A in the 0.3...3 A range) +/- 3...5 % earth fault current internal measurement current > 0.25 A in the 2.5...25 A range) +/- 3...5 % earth fault current internal measurement current > 0.7 A in the 7...70 A range) +/- 3...5 % earth fault current internal measurement current > 1 A in the 10...100 A range) +/- 2 % Temperature +/- 2 % THD measurement +/- 3...6 % power factor +/- 2...5 % active and reactive energy +/- 30 min/year internal clock","Overvoltage category":"III","Mechanical robustness":"Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-27 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27","Nbr. of units in pkg.":"1","Supply voltage limits":"85...265 V AC/DC","Associated fuse rating":"0.5 A gG control circuit","Maximum Operating Rate":"1800 cyc/h","Connections - terminals":"Control circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible with ferrule with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible with ferrule with cable end Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible stranded with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 14)flexible stranded with cable end Control circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)solid with cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1 mm²) AWG 24...AWG 14)solid with cable end","IP Degree of Protection":"IP20","Short-circuit withstand":"100 kA","Product or Component Type":"Motor controller","[Us] rated supply voltage":"100...240 V AC/DC 50/60 Hz","Current state 0 guaranteed":"Digital input 0...12 V 5 mA 10 ms","Current state 1 guaranteed":"Digital input 85...265 V 5 mA 10 ms","Communication Port Protocol":"Ethernet TCP/IP","Contacts type and composition":"2 NO fault signal 1 NO + 1 NC fault signal","[Ui] rated insulation voltage":"690 V AC IEC 60185","Maximum Output Switching Frequency":"2 Hz","Network and machine diagnosis type":"Motor statistics Motor status Event recording Running hours counter/operating time Number of starts and stops Running hours /stop hours counter Start curve showing motor start record Pre-alarms Trip history information Alarm counters","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...158 °F (-20...70 °C)","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$790.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e228a3237a7343bf3be575117425cb20.pdf","sourceUrl":"https://www.se.com/uk/en/product/LTMTEFM/motor-management-main-unit-tesys-tera-ethernet-ip-modbus-tcp-4-di-and-3-do-supply-100240vac-dc/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LTMTEFM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LTMTEFM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}