{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV432106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV432106","canonicalUrl":"https://aoctrl.com/schneider/LV432106","factsUrl":"https://aoctrl.com/api/mcp/products/LV432106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider LV432106 Compact Nsx — now discontinued, supplied from remaining surplus and broker stock.","salesMarkdown":"## Overview The LV432106 is a MicroLogic 6.3 A electronic trip unit for the Schneider ComPact NSX400...630 molded-case breaker range, rated 400 A on a 4-pole frame with LSIG protection (long-time, short-time, instantaneous, ground fault). It offers adjustable long-time and short-time delay settings, Zone Selective Interlocking (ZSI) for coordination, and an LCD display showing ammeter values, maintenance indicators, and event logs.","metaTitle":"Schneider LV432106 ComPact NSX MicroLogic 6.3 A trip unit, 4-pole, 400 A","metaDescription":"Schneider LV432106 MicroLogic 6.3 A electronic trip unit for ComPact NSX400...630, 4-pole, 400 A, LSIG protection, adjustable delays, ZSI, LCD display.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Range":"ComPact","Category":"US10DE201101","Standards":"UL 508 EN/IEC 60947-2","Display Type":"LCD display","Network type":"AC","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.3 A","Number of poles":"4P","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"mature","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Neutral position":"Left","Pollution degree":"3 IEC 60947-1","Range of Product":"ComPact NSX400...630","Network Frequency":"50/60 Hz","Device Application":"Distribution Generator","Type of Measurement":"Ammeter","Trip unit technology":"Electronic","Communication of data":"Time-stamped histories and event tables Maximeters/minimeters Demand current and power Maintenance indicators Power quality Instantaneous and demand values Energy metering Protection and alarm settings","Nbr. of units in pkg.":"1","IP degree of protection":"IP40 conforming to IEC 60529","Trip unit rated current":"400 A 104 °F (40 °C)","Earth-leakage protection":"Without","Electrical data recording":"Maintenance indicators","Product or Component Type":"Trip unit","Neutral protection settings":"0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t)","Protected poles description":"3t + N/2 3t 4t 3t + OSN","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Ambient Air Temperature for Storage":"-40...185 °F (-40...85 °C)","Ambient Air Temperature for Operation":"-13...158 °F (-25...70 °C)","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Adjustable","[Tr] Long-Time Protection Delay Adjustment Range":"15...400 s 1.5 x Ir 0.35...11 s 7.2 x Ir 0.5...16 s 6 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable","[Ir] long-time protection pick-up adjustment range":"160...400 A","[tsd] Short-time protection delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable","[Ig] ground-fault protection pick-up adjustment range":"0.4...1 x In In = 40 A 0.2...1 x In In > 40 A Ig enable on/off","[Ii] instantaneous protection pick-up adjustment range":"1.5...11 x In Compact NSX630 1.5...12 x In Compact NSX400","[Tg] Ground-Fault Protection Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$648.09","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9dbea73de98e2c0ca06314ba2aff480.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV432106/trip-unit-micrologic-6-3-a-for-compact-nsx-400-630-circuit-breakers-electronic-rating-400a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV432106/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV432106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV432106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}