{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV432977","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV432977","canonicalUrl":"https://aoctrl.com/schneider/LV432977","factsUrl":"https://aoctrl.com/api/mcp/products/LV432977","rawCanonicalId":null},"summary":{"shortDescription":"Circuit breaker, ComPact NSX630H, 70kA/415VAC, MicroLogic 2.3M trip unit 500A, 3 poles 3d","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPact","Depth (D)":"110 mm","Standards":"EN/IEC 60947","Width (W)":"140 mm","Height (H)":"255 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPact NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.3 M","Number of poles":"3P","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"mature","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"ComPact NSX400...630","Trip unit rating":"500 A at 65 °C","Device short name":"NSX630H","Network frequency":"50/60 Hz","Performance level":"H 70 kA 415 V AC","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"500 A at 65 °C","Downside connection":"Front","Motor tripping class":"20 10 5","Overvoltage category":"Class II","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"2000 cycles at 690 V In 6000 cycles at 690 V In/2 4000 cycles at 440 V In 8000 cycles at 440 V In/2","Mechanical durability":"15000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Protected poles description":"3t","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Phase unbalance","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"6 slot(s)","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"10 s at 7.2 x Ir for trip class 10 120 s at 1.5 x Ir for trip class 5 20 s at 7.2 x Ir for trip class 20 240 s at 1.5 x Ir for trip class 10 26 s at 6 x Ir for trip class 20 480 s at 1.5 x Ir for trip class 20 5 s at 7.2 x Ir for trip class 5 13.5 s at 6 x Ir for trip class 10 6.5 s at 6 x Ir for trip class 5","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"85 kA at 240 V AC 50/60 Hz conforming to UL 508 65 kA at 480 V AC 50/60 Hz conforming to UL 508 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","[Ii] instantaneous protection pick-up adjustment range":"6500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3dab1d3e6361cc4b885008167bf523d5.pdf","sourceUrl":"https://www.se.com/nz/en/product/LV432977/circuit-breaker-compact-nsx630h-70ka-415vac-micrologic-2-3m-trip-unit-500a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV432977/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV432977","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV432977 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}