{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV510482","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV510482","canonicalUrl":"https://aoctrl.com/schneider/LV510482","factsUrl":"https://aoctrl.com/api/mcp/products/LV510482","rawCanonicalId":null},"summary":{"shortDescription":"circuit breaker, EasyPact CVS250N, 50kA at 415VAC, 32A, TM-D trip unit, 4P3d","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Range":"EasyPact","Width":"140 mm","Height":"161 mm","Standards":"EN 60947-2 IEC 60947-2","Control type":"Toggle","Network type":"AC","Product name":"EasyPact CVS","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection (thermal) Short-circuit protection (magnetic)","lifecycle_stage":"mature","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Range of product":"EasyPact CVS100...250","Trip unit rating":"32 A at 40 °C","Device short name":"CVS100N","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Compatibility code":"CVS100","Device application":"Distribution","[In] rated current":"32 A at 40 °C","Downside connection":"Front","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"12000 cycles 415 V In conforming to IEC 60947-2","Mechanical durability":"30000 cycles","Breaking capacity code":"N","Connections - terminals":"Screw connection","IP degree of protection":"IP40","[Icu] Breaking capacity":"50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2","Product or component type":"Circuit breaker","Contact position indicator":"Yes","Neutral protection setting":"No protection (3D)","Protected poles description":"3D","Long time delay adjustment type":"Fixed","Short-time delay adjustment type":"Fixed","Electrical shock protection class":"Class II","Long time pick-up adjustment range":"0.7...1 x In","Ambient air temperature for storage":"-50...85 °C","Thermal protection adjustment range":"0...32 A","Long time pick-up adjustment type Ir":"Adjustable","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2","Earth leakage protection (Vigi add on)":"Without","Instantaneous pick-up adjustment range":"400 A","[Uimp] rated impulse withstand voltage":"8 kV conforming to EN/IEC 60947-2","Instantaneous pick-up adjustment type Ii":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b61b3975bebb41c86af8b645fc58c2e6.pdf","sourceUrl":"https://www.se.com/vn/en/product/LV510482/circuit-breaker-easypact-cvs250n-50ka-at-415vac-32a-tmd-trip-unit-4p3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV510482/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV510482","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV510482 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}