{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV838881","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV838881","canonicalUrl":"https://aoctrl.com/schneider/LV838881","factsUrl":"https://aoctrl.com/api/mcp/products/LV838881","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV838881, 800 A 3P drawout circuit breaker, L breaking capacity, 200 kA Icu at 240 V AC, UL 489, without Micrologic trip unit.","salesMarkdown":"The LV838881 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, rated 800 A continuous at 40 °C, 3-pole, with L breaking capacity (200 kA Icu at 240 V AC, 150 kA at 480 V, 100 kA at 600 V per UL 489). It ships without a Micrologic trip unit — you supply the trip unit separately. This is a protection device for main or feeder service in switchgear, sized for 800 A line current with a 9 ms maximum break time and 70 ms closing response. Schneider has marked the LV838881 obsolete. No official successor order code is available. The 30 kA short-time withstand (Icw) for 0.5 s per UL 489 means it holds through delayed tripping for selective coordination downstream. Drawout mounting allows the breaker to be racked out for maintenance or replacement without disturbing the bus connections.","metaTitle":"Schneider LV838881 MasterPact MTZ2 800A 3P Drawout, 200kA Ic","metaDescription":"LV838881 MasterPact MTZ2 800A 3P drawout circuit breaker, 200 kA Icu at 240 V AC, UL 489. Obsolete — sourced to order against RFQ. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"17.5 in (444.3 mm)","Height":"17.3 in (438.8 mm)","Control Type":"Push-button","Network type":"AC","Product name":"MasterPact MTZ2","Mounting Mode":"Drawout","lifecycle_stage":"current","Connection pitch":"4.5 in (115 mm)","Mounting Support":"Base plate Rails","Device short name":"MTZ2 08 L","Network Frequency":"50/60 Hz","Performance Level":"200 kA Icu 240 V AC 50/60 Hz UL 489 150 kA Icu 480 V AC 50/60 Hz UL 489 100 kA Icu 600 V AC 50/60 Hz UL 489","Poles description":"3P","Device Application":"Protection","Line Rated Current":"800 A 104 °F (40 °C)","Maximum breaking time":"9 ms","Nbr. of units in pkg.":"1","Breaking capacity code":"L","Circuit breaker CT rating":"800 A","Product or Component Type":"Circuit breaker","Integral instant protection":"72...88 kA","Maximum closing response time":"70 ms","Rated breaking and making capacity":"55 kA","[Icw] rated short-time withstand current":"30 kA 0.5 s UL 489"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/378e50f5055ffe07975f6415ae24eba0.pdf","sourceUrl":"https://www.se.com/us/en/product/LV838881/circuit-breaker-masterpact-mtz2-ul-489-max-800a-rated-3-pole-drawout-mount-l-breaking-cap-600vac-w-o-micrologic-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV838881/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for LV838881?","answer":"The breaker carries UL 489 listing. RoHS and REACH compliance documentation is standard for Schneider MasterPact products, but specific declarations should be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV838881","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV838881 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}