{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV838885","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV838885","canonicalUrl":"https://aoctrl.com/schneider/LV838885","factsUrl":"https://aoctrl.com/api/mcp/products/LV838885","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV838885, 1600A, 3-pole, drawout, L breaking capacity, 600VAC, UL 489, without Micrologic trip unit.","salesMarkdown":"The LV838885 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, rated 1600 A at 104 °F (40 °C), 3-pole, with L breaking capacity code. It's listed for 200 kA Icu at 240 V AC, 150 kA Icu at 480 V AC, and 100 kA Icu at 600 V AC under UL 489. The unit ships without a Micrologic trip unit, so you'll need to order that separately. The interrupting ratings (200 kA Icu at 240 V, 150 kA at 480 V, 100 kA at 600 V) tell you the maximum fault current the breaker can safely clear at those voltages; match these to your available fault current at the service entrance. The 30 kA short-time withstand current (Icw) for 0.5 s per UL 489 means the breaker can hold in during a delayed trip coordination scheme, which is key for selective coordination in a distribution panel.","metaTitle":"Schneider LV838885 MasterPact MTZ2 1600A 3P Drawout, Obsolet","metaDescription":"Schneider LV838885 MasterPact MTZ2 circuit breaker, 1600A, 3-pole, drawout, 200 kA Icu at 240V. Obsolete (L1). Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"17.5 in (444.3 mm)","Height":"17.3 in (438.8 mm)","Control Type":"Push-button","Network type":"AC","Product name":"MasterPact MTZ2","Mounting Mode":"Drawout","lifecycle_stage":"current","Connection pitch":"4.5 in (115 mm)","Mounting Support":"Base plate Rails","Device short name":"MTZ2 16 L","Network Frequency":"50/60 Hz","Performance Level":"200 kA Icu 240 V AC 50/60 Hz UL 489 150 kA Icu 480 V AC 50/60 Hz UL 489 100 kA Icu 600 V AC 50/60 Hz UL 489","Poles description":"3P","Device Application":"Protection","Line Rated Current":"1600 A 104 °F (40 °C)","Maximum breaking time":"9 ms","Nbr. of units in pkg.":"1","Breaking capacity code":"L","Circuit breaker CT rating":"1600 A","Product or Component Type":"Circuit breaker","Integral instant protection":"72...88 kA","Maximum closing response time":"70 ms","Rated breaking and making capacity":"55 kA","[Icw] rated short-time withstand current":"30 kA 0.5 s UL 489"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/62614529337506b2668b4d2b6f2a0e05.pdf","sourceUrl":"https://www.se.com/ca/en/product/LV838885/circuit-breaker-masterpact-mtz2-ul-489-max-1600a-rated-3-pole-drawout-mount-l-breaking-cap-600vac-w-o-micrologic-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV838885/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity code L mean?","answer":"The L breaking capacity code on this MasterPact MTZ2 indicates a standard interrupting rating level, as opposed to H (high) or S (superior) codes in the same family."},{"question":"Does LV838885 come with a trip unit?","answer":"No, the LV838885 ships without a Micrologic trip unit. You must order the trip unit separately to match your protection curve needs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV838885","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV838885 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}