{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV839095","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV839095","canonicalUrl":"https://aoctrl.com/schneider/LV839095","factsUrl":"https://aoctrl.com/api/mcp/products/LV839095","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Masterpact MTZ3 60 HC, LV839095, automatic switch disconnector, 6000 A, 3P, drawout, ANSI.","salesMarkdown":"The LV839095 is a Schneider Electric Masterpact MTZ3 60 HC automatic switch disconnector rated 6000 A at 104 °F (40 °C) — that's the continuous current it carries without derating in a typical 40 °C enclosure environment. The 200 kA Icu at 508 V AC (with external relay per ANSI C37.50) tells you the interrupting capacity available for fault clearing at that voltage; the same unit also carries 130 kA Icu at 635 V AC. For a 6000 A frame, those are high-end SCCR figures that give selectivity headroom downstream. This is a 3-pole drawout unit on a chassis mount, meaning the moving portion withdraws from the cassette for safe isolation and maintenance without unbolting power cables. The push-button control type covers the standard open/close/trip interface on the front escutcheon. Physical footprint: 31.07 in (789.1 mm) wide, 18.8 in (478.1 mm) tall, 16.8 in (426.8 mm) deep. The 9.06 in (230 mm) connection pitch matches standard bus-bar or cable-riser spacing in ANSI switchgear lineups. This is a drawout breaker — the cassette frame stays bolted to the chassis; the breaker element slides in and out on rails, so panel builders need to account for the full depth plus clearance for the racking mechanism. Single unit per package. The device short name MTZ3 60 HC identifies the frame size (MTZ3) and the high-capacity rating tier (60 HC). For a 6000 A drawout breaker at this interrupting capacity, lead time is typically project-quoted rather than off-the-shelf; submit an RFQ for the specific quantity and ship-to location.","metaTitle":"Schneider Electric LV839095 Masterpact MTZ3 60 HC, 6000A, 3P","metaDescription":"Schneider Electric LV839095 Masterpact MTZ3 60 HC switch disconnector. 6000 A rated, 200 kA Icu at 508 V AC, 3-pole drawout. Active production, available to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"31.07 in (789.1 mm)","title":"LV839095","Height":"18.8 in (478.1 mm)","description":"Automatic, switch disconnector, Masterpact MTZ3, 60 HC, 6000A, ANSI, 3P, drawout","Control Type":"Push-button","Network type":"AC","Mounting Mode":"Drawout","lifecycle_stage":"current","Connection pitch":"9.06 in (230 mm)","Mounting Support":"Chassis","Breaking capacity":"200.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 200.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 130.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50","Device short name":"MTZ3 60 HC","Network Frequency":"50/60 Hz","Poles description":"3P","Device Application":"Distribution","Nbr. of units in pkg.":"1","Product or Component Type":"Switch disconnector","[Ie] rated operational current":"6000 A 104 °F (40 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1e1f7f2a04337f43dfec288f2980b499.pdf","sourceUrl":"https://www.se.com/ca/en/product/LV839095/automatic-switch-disconnector-masterpact-mtz3-60-hc-6000a-ansi-3p-drawout/"},"ai":{"faq":[{"question":"Where can I buy LV839095 and how do I get a price?","answer":"The LV839095 is sourced to order against an RFQ through independent distribution. Submit a request for quote with your target quantity and delivery location; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to LV839095 in the Masterpact MTZ3 family?","answer":"Within the same MTZ3 frame, the primary variant difference is the continuous current rating and interrupting capacity tier. The LV839095 is the 6000 A 60 HC (high-capacity) version. Lower-amp or standard-capacity siblings in the same drawout 3P ANSI format share the same cassette footprint but carry different SCCR curves — verify coordination studies before substituting."},{"question":"What is LV839095's listed depth?","answer":"The LV839095 has a depth of 16.8 in (426.8 mm). This is the overall depth of the drawout breaker element; the fixed cassette may add additional depth behind the panel."},{"question":"What is LV839095's listed width?","answer":"The LV839095 has a width of 31.07 in (789.1 mm). This is the overall width of the drawout breaker element."},{"question":"What compliance documentation does Schneider provide for LV839095?","answer":"The LV839095 is designed and tested to ANSI C37.50 standards for low-voltage power circuit breakers. The interrupting capacity ratings (200 kA Icu at 508 V AC, 130 kA Icu at 635 V AC) are certified under that standard with the specified external relay. Specific RoHS, REACH, or UL documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV839095","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV839095 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}