{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV839099","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV839099","canonicalUrl":"https://aoctrl.com/schneider/LV839099","factsUrl":"https://aoctrl.com/api/mcp/products/LV839099","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV839099, 3-pole drawout circuit breaker, 1600 A rated at 40 °C, L1F breaking capacity, 200 kA Icu at 254 V AC.","salesMarkdown":"The LV839099 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 1600 A continuous at 40 °C ambient. That 1600 A frame covers large secondary transformers, main feeders, or generator incomers in ANSI-distribution gear. The L1F breaking capacity code delivers 200 kA Icu at 254 V AC and 130 kA Icu at 635 V AC per ANSI C37.50 — meaning it can safely interrupt fault currents up to that level without upstream cascading. Short-time withstand (Icw) is 22 kA for 0.5 s, which governs coordination with downstream breakers during a delayed trip. Mechanical endurance is 12,500 cycles, electrical endurance 2,800 cycles under ANSI C37.50. The integral instantaneous protection is set at 49.5 to 55.5 kA — a fixed magnetic range for bolted-fault clearing. Maximum break time is 9 ms, closing response 70 ms. Drawout mounting (4.5-inch connection pitch) means the breaker slides onto base-plate rails for racking in and out without disturbing power wiring — standard for switchgear where isolation for maintenance is required.","metaTitle":"Schneider LV839099 MasterPact MTZ2 1600A 3P Drawout, 200kA I","metaDescription":"Schneider Electric LV839099 MasterPact MTZ2 circuit breaker, 1600A rated, 3-pole drawout, 200 kA Icu at 254 VAC. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"17.5 in (444.3 mm)","Height":"17.3 in (438.8 mm)","Application":"Protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"4.5 in (115 mm)","Electrical Life Cycles":"2800 cycles ANSI C37.50","Mechanical Life Cycles":"12500 cycles ANSI C37.50","Main Product Or Component Type":"Circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5022104c2e9d4eb06d6aaf1a25f2cf6b.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV839099/circuit-breaker-masterpact-mtz2-ansi-max-1600a-rated-3-pole-drawout-mount-l1f-breaking-cap-635vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV839099/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV839099","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV839099 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}