{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV839195","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV839195","canonicalUrl":"https://aoctrl.com/schneider/LV839195","factsUrl":"https://aoctrl.com/api/mcp/products/LV839195","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV839195, 3-pole drawout circuit breaker, 1600 A at 40 °C, breaking capacity, 635 VAC, with ArcBlok.","salesMarkdown":"It carries 200 kA Icu at 254 VAC 60 Hz per ANSI C37.50, tapering to 100 kA Icu at 635 VAC 50 Hz. The drawout cradle isolates the breaker from the bus for safe racking without unbolting main lugs — standard for switchgear lineups where a unit can be rolled out for maintenance while the bus stays live. The breaking capacity code means the interrupting ratings follow the curve: 200 kA at 254 VAC 60 Hz, 150 kA at 508 VAC 50 Hz, and 100 kA at 635 VAC 50 Hz. The integral instantaneous protection trips between 72 and 88 kA — that is the magnetic-only pickup for bolted faults; the electronic trip unit (not listed here) handles the time-current curves for coordination. ## Integration Notes Drawout mounting means the breaker slides into a fixed cradle with primary disconnects and control wiring stabs. The base plate rails and 4.5 in (115 mm) connection pitch match standard ANSI switchgear cubicle cutouts. Overall dimensions: 17.5 in wide × 17.3 in tall × 16.8 in deep (444.3 × 438.8 × 426.8 mm). Mechanical durability is rated at 10,000 cycles per ANSI C37.50; electrical durability at 1,000 cycles under rated conditions. Maximum breaking time is 9 ms, closing response time 70 ms — both within typical ANSI metal-clad switchgear requirements for fast fault clearing.","metaTitle":"Schneider LV839195 MasterPact MTZ2, 1600A, 3P, Drawout, Obso","metaDescription":"Schneider Electric MasterPact MTZ2 LV839195 circuit breaker, 1600A at 40°C, 3-pole, drawout, L1 breaking capacity, 635VAC. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"17.5 in (444.3 mm)","Height":"17.3 in (438.8 mm)","Application":"Protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"4.5 in (115 mm)","Safety Category":"200 kA Icu 254 V AC 60 Hz ANSI C37.50 200 kA Icu 508 V AC 60 Hz ANSI C37.50 130 kA Icu 635 V AC 60 Hz ANSI C37.50 200 kA Icu 254 V AC 50 Hz ANSI C37.50 150 kA Icu 508 V AC 50 Hz ANSI C37.50 100 kA Icu 635 V AC 50 Hz ANSI C37.50","Electrical Life Cycles":"1000 cycles ANSI C37.50","Mechanical Life Cycles":"10000 cycles ANSI C37.50","Main Product Or Component Type":"Circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c15699496f0243980ba8dfe490b16ef.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV839195/circuit-breaker-masterpact-mtz2-ansi-max-1600a-rated-3-pole-drawout-mount-l1-breaking-cap-635vac-w-arcblok/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV839195/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV839195","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV839195 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}