{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV839225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV839225","canonicalUrl":"https://aoctrl.com/schneider/LV839225","factsUrl":"https://aoctrl.com/api/mcp/products/LV839225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ series, MX communicating opening voltage release, LV839225, 12 V DC control circuit, drawout mounting, response time 50 ms.","salesMarkdown":"The LV839225 is an MX communicating opening voltage release from the MasterPact MTZ family, designed for drawout mounting. It operates on a 12 V DC control circuit and triggers the breaker trip when the control voltage drops to between 0.7 and 1.1 times the rated Un. Response time is 50 ms ± 10% across MTZ1, MTZ2, and MTZ3 frames — consistent enough for coordinated protection schemes where the opening coil must clear before downstream devices. The drawout mounting means this coil is intended for the removable chassis of a MasterPact MTZ breaker — it is not a fixed-mount accessory. The 12 V DC control voltage is the nominal coil supply; the tripping threshold of 0.7 to 1.1 Un means the coil will release the breaker when the control voltage falls to roughly 8.4 V DC or rises to 13.2 V DC, providing undervoltage protection. The holding power of 4.5 VA / 4.5 W is the steady-state draw once the coil is energized — relevant for sizing the control transformer or DC supply feeding the trip circuit. ## Deployment context This coil mounts into the drawout cradle of a MasterPact MTZ air circuit breaker — common in main switchboards, generator paralleling gear, and large motor control centers where the breaker must be removable for maintenance without disturbing line-side connections. The MX communication variant allows the trip signal to be initiated remotely via the breaker's communication network, which is typical in automated power distribution systems.","metaTitle":"LV839225 MX communicating opening coil, 12 V DC, for MTZ dra","metaDescription":"LV839225 MX communicating opening voltage release, 12 V DC, for MasterPact MTZ drawout. Obsolete — sourced to order against RFQ. Response time 50 ms.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Application":"Control","Coil Voltage":"12 V DC","Product Status":"Active","Main Product Or Component Type":"Voltage release"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5303f4b2c019c63c4ac56a2b4599f5b.pdf","sourceUrl":"https://www.se.com/us/en/product/LV839225/mx-communicating-opening-voltage-release-12-v-dc-for-mtz-drawout/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV839225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV839225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV839225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}