{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV839308","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV839308","canonicalUrl":"https://aoctrl.com/schneider/LV839308","factsUrl":"https://aoctrl.com/api/mcp/products/LV839308","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ3, LV839308, 3-pole drawout ANSI circuit breaker, 5000 A rated current, H2 breaking capacity (85 kA Icu at 508 VAC), 635 VAC, without Micrologic trip unit, with ArcBlok.","salesMarkdown":"The LV839308 is a MasterPact MTZ3 drawout circuit breaker rated 5000 A continuous at 40 °C — that's the full-frame current, not a derated number, so it handles a 5000 A bus without forced cooling. The H2 breaking capacity code delivers 85 kA Icu at 508 VAC (per ANSI C37.50), which covers most industrial secondary-distribution fault levels in North America. The 170 kA rated breaking and making capacity tells you it can close into and interrupt a bolted fault at that level, critical for coordination studies. The 85 kA short-time withstand (Icw) for 0.5 s means it holds through delayed trips downstream — selectivity headroom for a multi-level distribution scheme. ## Deployment context Drawout mounting on base plate rails means the breaker slides into a fixed cradle — no bolted bus connections to torque. That cuts swap time during maintenance or fault replacement to minutes, not hours. The 3-pole configuration suits 3-phase AC distribution in switchgear lineups. The 50/60 Hz network frequency covers both 60 Hz North American and 50 Hz global installations without a de-rate.","metaTitle":"LV839308 MasterPact MTZ3 3P Drawout 5000A H2 635VAC Circuit","metaDescription":"LV839308 MasterPact MTZ3 ANSI circuit breaker, 3-pole drawout, 5000 A rated, H2 breaking capacity (85 kA Icu at 508 VAC), 635 VAC, without Micrologic trip unit. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"16.8 in (426.8 mm)","Width":"31.07 in (789.1 mm)","Height":"18.8 in (478.1 mm)","Application":"Protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"9.06 in (230 mm)","Safety Category":"85 kA Icu 254 V AC 50/60 Hz ANSI C37.50 85 kA Icu 508 V AC 50/60 Hz ANSI C37.50 85 kA Icu 635 V AC 50/60 Hz ANSI C37.50","Electrical Life Cycles":"2800 cycles ANSI C37.50","Mechanical Life Cycles":"12500 cycles ANSI C37.50","Main Product Or Component Type":"Circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/08ee7dcd7d09a53e5b4346e2b846d347.pdf","sourceUrl":"https://www.se.com/ca/en/product/LV839308/circuit-breaker-masterpact-mtz3-ansi-max-5000a-rated-3-pole-drawout-mount-h2-breaking-cap-635vac-w-o-micrologic-trip-unit-w-arcblok/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV839308/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV839308","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV839308 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}