{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846162","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846162","canonicalUrl":"https://aoctrl.com/schneider/LV846162","factsUrl":"https://aoctrl.com/api/mcp/products/LV846162","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, fixed circuit breaker, 3P, 1250 A at 40 °C, H2V 100 kA at 415 V AC, push-button control, without control unit.","salesMarkdown":"The Schneider LV846162 is a MasterPact MTZ2 fixed-mount circuit breaker, 3-pole, rated 1250 A at 40 °C. It belongs to the H2V performance tier — 100 kA ultimate breaking capacity (Icu) at 440 V AC, 50/60 Hz, and the same 100 kA service breaking (Ics). That means it clears a fault up to 100 kA and stays functional afterward, no immediate replacement needed. Category B selectivity (per EN/IEC 60947-2) lets it coordinate with downstream breakers so only the faulted branch trips — critical for a production line where you want the main breaker to hold while a feeder clears. Rated operational voltage is 440 V AC, insulation voltage 1000 V AC, impulse withstand 12 kV. Short-time withstand (Icw) holds 100 kA for 0.5 s and 1 s, 75 kA for 3 s — enough for selective coordination with downstream devices. Mounting is fixed on rails or base plate, connection pitch 115 mm. Both upside and downside connections accept front or rear terminations — common in switchboard builds where cable routing differs between incoming and outgoing sections. IP30 protection; inside a panel that's fine, but keep it out of direct washdown zones. Also meets IEC 61557-12 for insulation monitoring. Isolation suitability is confirmed per EN/IEC 60947-2 — the breaker provides visible isolation when open. Altitude derating above 2000 m is specified, so check if your installation is above that.","metaTitle":"Schneider LV846162 MasterPact MTZ2 1250A 3P Circuit Breaker,","metaDescription":"Schneider LV846162 MasterPact MTZ2 fixed circuit breaker, 1250 A rated, 100 kA breaking at 440 V AC, 3 poles. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"422 mm","Height":"352 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,037.85","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f1c0b802c5a7d398a56e707b316e3dbe.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV846162/circuit-breaker-frame-masterpact-mtz2-12h2v-fixed-for-micrologic-x-1250a-100ka-415vac-icu-icw-3p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846162/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846162","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846162 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}