{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846164","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846164","canonicalUrl":"https://aoctrl.com/schneider/LV846164","factsUrl":"https://aoctrl.com/api/mcp/products/LV846164","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV846164, 3P fixed circuit breaker, 2000 A rated current, 100 kA breaking capacity at 440 V AC, H2V performance level.","salesMarkdown":"The LV846164 is a fixed-mount MasterPact MTZ2 circuit breaker, 3-pole, rated 2000 A at 40 °C. That 2000 A continuous current handles the main feed of a large distribution board or a high-load industrial bus. The H2V performance grade delivers 100 kA ultimate breaking capacity (Icu) at 440 V AC — enough to clear a bolted fault on a transformer secondary without upstream coordination issues. Category B selectivity means it holds full discrimination with downstream breakers, so a fault on a branch won't drop the main. The short-time withstand (Icw) is 100 kA for 0.5 s and 1 s, and 75 kA for 3 s — that's the thermal and dynamic stress the breaker can carry during a delayed trip. For selective coordination schemes where the main breaker waits for a downstream device to clear, this Icw rating is the number that governs. The making capacity (Icm) of 220 kA at 440 V AC confirms the contacts can close into a fault without welding. Mounting is fixed on rails or a base plate, with front or rear connections on both the line and load sides. The 422 mm width, 352 mm height, and 300 mm depth fit a standard switchboard cubicle — plan for the 115 mm connection pitch when laying out busbars. IP30 protection suits indoor panel installation; no additional enclosure needed for dust or drip protection. ## Standards and compliance — what the approvals cover The breaker complies with EN/IEC 60947-1 (general rules), EN/IEC 60947-2 (circuit breakers), and EN/IEC 60947-2 Annex H (selective breakers). It also meets IEC 61557-12 for performance measurement in power distribution. ## Durability and thermal — cycles and dissipation Mechanical durability is 15,000 cycles with periodic preventive maintenance. Electrical durability under AC-23A (frequent switching of motor loads) is 8,000 cycles at 440 V AC and rated current; under AC-3 (direct switching of motors) it is 6,000 cycles. Power dissipation at rated current is 250 W — factor that into cabinet ventilation calculations.","metaTitle":"Schneider Electric MasterPact MTZ2 LV846164, 2000 A, 100 kA","metaDescription":"LV846164 MasterPact MTZ2 3P fixed circuit breaker, 2000 A, 100 kA breaking capacity at 440 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"422 mm","Height":"352 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Mechanical Life Cycles":"15000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$6,075.54 – $15,112.99","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ffce4baa640252b735c3cfdbe80e535.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV846164/circuit-breaker-frame-masterpact-mtz2-20h2v-fixed-for-micrologic-x-2000a-100ka-415vac-icu-icw-3p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846164/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846164","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846164 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}