{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846187","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846187","canonicalUrl":"https://aoctrl.com/schneider/LV846187","factsUrl":"https://aoctrl.com/api/mcp/products/LV846187","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MasterPact MTZ2, fixed circuit breaker, 4000 A at 40 °C, H2V 100 kA at 415 V AC, 4P, without control unit.","salesMarkdown":"The LV846187 is a fixed-mount MasterPact MTZ2 air circuit breaker from Schneider Electric's MasterPacT range, rated 4000 A at 40 °C with an H2V performance class delivering 100 kA interrupting capacity at 415 V AC. It's a 4-pole unit without an integral control unit, intended for power distribution protection in Category B selective coordination schemes. The H2V rating means 100 kA Icu at 415 V AC and 100 kA Ics at 440 V AC — the service breaking capacity equals the ultimate, so the breaker clears a fault and is immediately ready to reclose without derating. Short-time withstand (Icw) is 100 kA for 1 s, which supports full selectivity with downstream breakers in a distribution panel. Fixed-mount chassis with 537 mm width, 352 mm height, and 300 mm depth. Connection pitch is 115 mm; both front and rear connections are available on the upside and downside. Mounts on rails or a base plate.","metaTitle":"Schneider Electric LV846187 MasterPact MTZ2 4000A Circuit Br","metaDescription":"Schneider Electric LV846187 MasterPact MTZ2 fixed circuit breaker, 4000 A at 40 °C, H2V 100 kA at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"300 mm","Width":"537 mm","Height":"352 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP30","Application":"Power distribution protection","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front Rear","Electrical Life Cycles":"5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Mechanical Life Cycles":"15000 cycles with periodic preventive maintenance","Connection Surface Bottom":"Front Rear","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$20,929.59 – $23,290.29","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/155b9e572e80cfb060093dd77d490b61.pdf","sourceUrl":"https://www.se.com/il/en/product/LV846187/circuit-breaker-masterpact-mtz2-40-h2v-4000-a-4-poles-fixed-without-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LV846187/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846187","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846187 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}