{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846194","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846194","canonicalUrl":"https://aoctrl.com/schneider/LV846194","factsUrl":"https://aoctrl.com/api/mcp/products/LV846194","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT series, MasterPact MTZ2, circuit breaker, LV846194, 4 poles, 2000 A rated current, 100 kA breaking capacity at 440 V AC, drawout mounting.","salesMarkdown":"The Schneider Electric LV846194 is a MasterPact MTZ2 drawout circuit breaker in the MasterPacT range, rated 2000 A at 40 °C with 4 poles and a Category B selectivity profile. The 12 kV impulse withstand voltage (Uimp) and 100 kA short-time withstand (Icw) for 1 second confirm it coordinates with downstream devices in a selective distribution scheme. The 100 kA Ics at 440 V AC means the breaker can interrupt a fault at that level and be returned to service; the 220 kA Icm making capacity ensures it closes against an existing fault without welding contacts. Electrical durability of 8000 cycles at rated current under AC-23A duty covers frequent switching of motor loads; mechanical durability of 15000 cycles with periodic maintenance governs the mechanism life. The 25 ms maximum breaking time and 70 ms closing response are coordination parameters for arc-flash studies and selective tripping schemes.","metaTitle":"Schneider Electric LV846194 MasterPact MTZ2 4P 2000A Circuit","metaDescription":"Schneider Electric LV846194 MasterPact MTZ2 4P drawout circuit breaker, 2000 A rated current, 100 kA breaking capacity at 440 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"403 mm","Range":"MasterPacT","Width":"556 mm","title":"LV846194","Height":"439 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ2 20H2V drawout for MicroLogic X, 2000A, 100kA/415VAC (Icu/Icw), 4P","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Drawout","Sensor rating":"1000 A 1250 A 1600 A 2000 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Left","Performance type":"H2V 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 20 H2V","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"2000 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"15000 cycles with periodic preventive maintenance","Power dissipation in W":"470 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"100 kA 0.5 s 100 kA 1 s 75 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$8,003.34 – $19,431.93","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d373ed20454cbd239db2f214517ad57a.pdf","sourceUrl":"https://www.se.com/au/en/product/LV846194/circuit-breaker-frame-masterpact-mtz2-20h2v-drawout-for-micrologic-x-2000a-100ka-415vac-icu-icw-4p/"},"ai":{"faq":[{"question":"What compliance documentation does Schneider Electric provide for LV846194?","answer":"The LV846194 carries EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12 certifications. It is suitable for isolation per EN/IEC 60947-2. Specific RoHS, REACH, and UL documentation should be requested at quote time as the evidence does not list those marks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846194","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846194 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}