{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846200","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846200","canonicalUrl":"https://aoctrl.com/schneider/LV846200","factsUrl":"https://aoctrl.com/api/mcp/products/LV846200","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2 fixed circuit breaker, LV846200, 800 A at 40 °C, 4 poles, H2V 100 kA 415 V AC, Category B, IP30.","salesMarkdown":"The LV846200 is a MasterPact MTZ2 fixed-mount circuit breaker rated 800 A at 40 °C with a service breaking capacity of 100 kA at 440 V AC. The H2V performance class confirms the 100 kA rating at 415 V AC, so you're covered across the common 400 V class supply voltages. Category B selectivity means the breaker has intentional short-time delay, so it coordinates with downstream devices: a fault on a branch feeder trips the branch breaker first, not this main. That avoids a full panel blackout for a single load fault. The 4-pole design with neutral on the right suits 3-phase + N distribution. Fixed mounting on rails or base plate with front and rear connection options gives flexibility for panel layout — the 115 mm connection pitch matches standard busbar spacing. IP30 keeps fingers out but expects enclosure protection against water. ## Durability and thermal budget Mechanical durability of 15,000 cycles with periodic preventive maintenance and electrical durability of 10,000 cycles at rated current under AC-23A. Maximum breaking time of 25 ms and closing response time of 70 ms are within typical main-breaker coordination windows.","metaTitle":"Schneider Electric LV846200 MasterPact MTZ2 800A 4P Circuit","metaDescription":"LV846200 MasterPact MTZ2 fixed circuit breaker, 800 A rated at 40 °C, 4 poles, H2V 100 kA at 415 V AC. EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"300 mm","Range":"MasterPacT","Width":"537 mm","title":"LV846200","Height":"352 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ2 08H2V fixed for MicroLogic X, 800A, 100kA/415VAC (Icu/Icw), 4P right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Fixed","Sensor rating":"400 A 630 A 800 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H2V 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 08 H2V","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"800 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"15000 cycles with periodic preventive maintenance","Power dissipation in W":"42 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"100 kA 0.5 s 100 kA 1 s 75 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,422.87","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/219161da84d88e32aa122d8740c969e0.pdf","sourceUrl":"https://www.se.com/ie/en/product/LV846200/circuit-breaker-frame-masterpact-mtz2-08h2v-fixed-for-micrologic-x-800a-100ka-415vac-icu-icw-4p-right-neutral/"},"ai":{"faq":[{"question":"Who supplies LV846200 and how is it quoted for volume purchases?","answer":"The LV846200 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to LV846200 in the MasterPact MTZ2 family?","answer":"The LV846200 is a specific variant: 800 A, 4-pole, H2V 100 kA, fixed mount. A different rating (e.g., 630 A or 1000 A) or a different performance class (e.g., H1 or H3) would change the breaking capacity or current — not a direct pin-compatible swap. Review the MTZ2 selection guide for the exact rating and performance class your coordination study requires."},{"question":"What is LV846200's listed depth?","answer":"The depth is 300 mm."},{"question":"What compliance documentation does this brand provide for LV846200?","answer":"The breaker is designed to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H, plus IEC 61557-12. The manufacturer typically provides a Declaration of Conformity and test reports for these standards upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}