{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846206","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846206","canonicalUrl":"https://aoctrl.com/schneider/LV846206","factsUrl":"https://aoctrl.com/api/mcp/products/LV846206","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPact MTZ2, LV846206, fixed-mount circuit breaker, 4P, 3200 A at 40 °C, H2V 100 kA at 415 V AC, IP30.","salesMarkdown":"The Schneider Electric LV846206 is a MasterPact MTZ2 fixed-mount air circuit breaker, 4-pole, rated 3200 A at 40 °C. It's built for main switchboard and large distribution protection — the kind of gear that sits on a base plate or rails in a utility or industrial substation, not a panelboard. It's Category B selectivity per IEC 60947-2, so you can coordinate it downstream without sacrificing uptime on a fault. The 100 kA Ics at 440 V AC is the service breaking capacity — the breaker clears that fault and is still usable afterward, not just a one-shot Icu. The Icw is 100 kA for 1 second, which gives you real headroom for short-time delay coordination with downstream feeders. That 75 kA for 3 seconds matters if your protection scheme needs a longer clearing window. Insulation voltage Ui is 1000 V AC, impulse withstand Uimp is 12 kV — this breaker is rated for the heavy end of low-voltage distribution. Fixed-mount version — no draw-out cradle. The 537 mm width, 352 mm height, and 300 mm depth give you the envelope for a dedicated cell in a switchboard. Connection pitch is 115 mm, and both front and rear connections are available for the upside and downside. Neutral is on the right. ## Durability and thermal budget Mechanical durability is 15,000 cycles with periodic preventive maintenance — that's typical for a main breaker that sees infrequent switching. Electrical durability at rated current is 5,000 cycles at 440 V AC under AC-23A duty. Power dissipation is 420 W at full load, so factor that into your switchgear ventilation. Altitude derating above 2000 m is specified.","metaTitle":"Schneider Electric LV846206 MasterPact MTZ2, 3200 A, 100 kA","metaDescription":"Schneider Electric LV846206 MasterPact MTZ2 circuit breaker. 3200 A rated current, 100 kA breaking capacity at 415 V AC. Active production. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"300 mm","Range":"MasterPacT","Width":"537 mm","title":"LV846206","Height":"352 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"Circuit breaker frame, MasterPact MTZ2 32H2V fixed for MicroLogic X, 3200A, 100kA/415VAC (Icu/Icw), 4P right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Fixed","Sensor rating":"1600 A 2000 A 2500 A 3200 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H2V 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 32 H2V","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"3200 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"15000 cycles with periodic preventive maintenance","Power dissipation in W":"420 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"100 kA 0.5 s 100 kA 1 s 75 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$14,611.32","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5c43217f6ca422d69bb1a1cf49e53676.pdf","sourceUrl":"https://www.se.com/vn/en/product/LV846206/circuit-breaker-frame-masterpact-mtz2-32h2v-fixed-for-micrologic-x-3200a-100ka-415vac-icu-icw-4p-right-neutral/"},"ai":{"faq":[{"question":"Where can I buy LV846206 and how do I get a price?","answer":"The LV846206 is sourced to order through independent distribution. Submit an RFQ — availability and current pricing are confirmed at quote time. No stock count or price figure is published here."},{"question":"What is LV846206's listed depth?","answer":"The LV846206 has a depth of 300 mm. Overall dimensions are 537 mm wide by 352 mm high."},{"question":"What compliance documentation does this breaker carry?","answer":"The LV846206 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2. The IP30 rating is per EN 60529. Pollution degree 3 is per IEC 60947-1."},{"question":"What is the closest alternative to LV846206 in this family?","answer":"Within the MasterPact MTZ2 fixed-mount range, the closest alternative would be a different current rating or performance class — for example, a 2500 A H2V variant if the load doesn't require the full 3200 A. No pin-compatible drop-in exists; the frame size and connection pitch differ by rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846206","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846206 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}