{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LV846210","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LV846210","canonicalUrl":"https://aoctrl.com/schneider/LV846210","factsUrl":"https://aoctrl.com/api/mcp/products/LV846210","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric MasterPacT MasterPact MTZ2 08 H2V, drawout circuit breaker, 4P, 800 A at 40 °C, 100 kA Ics at 440 V AC, H2V performance level.","salesMarkdown":"## MasterPact MTZ2 08 H2V — 800 A Drawout Breaker, 100 kA Ics The Schneider Electric LV846210 is a MasterPact MTZ2 08 H2V drawout circuit breaker, part of the MasterPacT range. The H2V performance level delivers 100 kA Ics (service breaking capacity) at 440 V AC 50/60 Hz, with a corresponding Icm (making capacity) of 220 kA at the same voltage. This SCCR headroom allows the breaker to clear high-fault currents without upstream coordination issues in Category B selective systems. Rated insulation voltage (Ui) is 1000 V AC, impulse withstand (Uimp) is 12 kV, and short-time withstand (Icw) is 100 kA for 0.5 s or 1 s, and 75 kA for 3 s. Maximum breaking time is 25 ms, with a closing response time of 70 ms. ## Drawout Mounting and Integration Drawout mounting allows the breaker to be racked in and out of the cassette without disturbing power or control wiring — essential for maintenance and safe isolation in metal-enclosed switchgear. Mounting support options include rails or a base plate. Connection pitch is 115 mm, and both upside and downside connections are available in front or rear configurations. Dimensions are 556 mm wide × 439 mm high × 403 mm deep. The neutral pole is on the right. Control is via push-button; the unit ships without a separate control unit. ## Environmental and Standards Compliance Operates in ambient temperatures from -25 to 70 °C, stores from -40 to 85 °C. IP30 protection per EN 60529. Power dissipation is 100 W at rated current. Meets EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Electrical durability is 10,000 cycles at 440 V AC under AC-23A, 6,000 cycles under AC-3. Mechanical durability is 15,000 cycles with periodic preventive maintenance.","metaTitle":"Schneider LV846210 MasterPact MTZ2 08 H2V, 800 A, 100 kA","metaDescription":"Schneider Electric LV846210 MasterPact MTZ2 08 H2V drawout circuit breaker. 800 A at 40 °C, 4P, 100 kA Ics at 440 V AC. Current production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"403 mm","Range":"MasterPacT","Width":"556 mm","title":"LV846210","Height":"439 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12","description":"circuit breaker, Masterpact MTZ2 08 H2V, 800 A, 4 poles, drawout, without trip unit, right neutral","Control type":"Push-button","Control unit":"Without control unit","Product name":"MasterPact MTZ2","Mounting mode":"Drawout","Sensor rating":"400 A 630 A 800 A","lifecycle_stage":"current","Connection pitch":"115 mm","Mounting support":"Rails Base plate","Neutral position":"Right","Performance type":"H2V 100 kA 415 V AC","Pollution degree":"3 conforming to IEC 60947-1","Device short name":"MTZ2 08 H2V","Poles description":"4P","Upside connection":"Front Rear","Device application":"Power distribution protection","Operating altitude":"0...2000 m without derating 2000...5000 m with derating","[In] rated current":"800 A at 40 °C","Downside connection":"Front Rear","Selectivity category":"Category B","Electrical durability":"10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3","Maximum breaking time":"25 ms","Mechanical durability":"15000 cycles with periodic preventive maintenance","Power dissipation in W":"100 W","IP degree of protection":"IP30 conforming to EN 60529","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"12 kV","[Icw] rated short-time withstand current":"100 kA 0.5 s 100 kA 1 s 75 kA 3 s","[Icm] rated short-circuit making capacity":"220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,481.73","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/60150e9a4ac432fbf360f476f6e820b4.pdf","sourceUrl":"https://www.se.com/il/en/product/LV846210/circuit-breaker-masterpact-mtz2-08-h2v-800-a-4-poles-drawout-without-trip-unit-right-neutral/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LV846210?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — no automated figures are published for this high-current drawout breaker."},{"question":"What is the closest pin-compatible alternative to LV846210 in this component family?","answer":"Within the MasterPact MTZ2 family, the closest alternative would be a different H2V performance level or ampere rating (e.g., MTZ2 06 H2V at 630 A). However, the LV846210 is a specific 800 A, 4P, drawout variant; any substitution requires verifying the sensor rating (400–800 A range) and frame size."},{"question":"What is LV846210's listed depth (403 mm) on this component line?","answer":"The LV846210 has a depth of 403 mm. This is the dimension from the front of the breaker to the rear, relevant for enclosure depth planning."},{"question":"What is LV846210's listed range (MasterPacT) on this component line?","answer":"The LV846210 belongs to the MasterPacT range, specifically the MasterPact MTZ2 series. This is Schneider Electric's high-performance air circuit breaker platform for main and feeder protection."},{"question":"What compliance documentation does this brand provide for LV846210 (RoHS, REACH, UL, IEC)?","answer":"The LV846210 is certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2. For RoHS/REACH declarations and UL listing status, request the specific compliance documentation with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LV846210","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LV846210 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}